• Evacuation Announcement interval (SW4-4 through SW4-8)

Time intervals can be set for 30 seconds to 15 minutes 30 seconds in 30 seconds units.

• All-zone announcement interval (SW2-3 through SW2-8)

Time intervals can be set for "OFF", "0 second" or "30 seconds to 15 minutes 30 seconds" in 30 seconds
units.

• Warning Announcement (SW3-2 through SW3-8)

Set "repeat yes or no", "number of repeats", "repeat intervals", and "repeat mode" for the Warning
Announcement.

SW4

ON

OFF

4

0

8 minutes

5

0

4 minutes

6

0

2 minutes

7

0

1 minute

8

0

30 seconds

SW4

Evacuation Announcement interval

ON

1 2 3 4 5 6 7 8

SW2

ON

OFF

3

Off

On

4

0

8 minutes

5

0

4 minutes

6

0

2 minutes

7

0

1 minute

8

0

30 seconds

SW2

All-zone announcement interval

ON

1 2 3 4 5 6 7 8

SW3

ON

OFF

2

Termination

Resumption

SW3

Repeat mode

No. of repeats

Repeat interval

Repetition

ON

1 2 3 4 5 6 7 8

3

+0

+2

4

+0

+1

5

No

Yes

6

0 minute

1 minute

7

0 second

30 seconds

8

0 second

15 seconds

Memo
• "Resumption": Warning Announcement interrupted by a PA microphone announcement is resumed after

microphone announcement completion.

• "Termination": Warning Announcement is terminated when a PA microphone announcement is made. (It is

not resumed even when the microphone announcement is completed.)

• Number of repeats: Warning Announcement is repeated twice when the SW3-3 and SW3-4 switches are

both set to OFF. If, for example, the SW3-3 switch (+2) is set to ON, the number of repeats increases by
two, causing the Warning Announcement to be repeated four times.