Carrier 38AH044-134 User Manual

Page 16

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 6A — Refrigerant Piping Requirements — 38AH044-104 Dual-Circuit Units — 60 Hz

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)

UNIT 38AH

15-25

25-50

50-75

75-100

100-150

150-200

(4.6-7.6)

(7.6-15.2)

(15.2-22.9)

(22.9-30.5)

(30.5-45.7)

(45.7-61.0)

L

s

L

S

L

S

L

S

L

S

L

s

044

Ckt A

%

1%

У8

1У8

Ув

2Ув

Уе

2Уе

Уе

2Ув

Va

2Ув

Ckt В

%

1%

У8

1%

Ув

2Ув

Ув

2Ув

Va

2Уе

Va

2Ув

054

Ckt A

%

1%

У8

1%

Ув

2Ув

Va

2Ув

Va

2Ув

Va

2Ув

Ckt В

У8

1%

У8

2У8

Ув

2Ув

1Ув

2Ув

1Ув

2Ув

1У8

2%*

064

Ckt A

%

1%

У8

2Ув

Ув

2Ув

Уе

2Ув

1Уе

2Ув

1Ув

2%t

Ckt В

%

2Ve

У8

2Ув

Ув

2Ув

1Ув

2Ув

1У8

2%

1У8

2%

074

Ckt A

%

2Ve

У8

2Уа

Ув

2Ув

1Ув

2Ув

1Ув

2%t

1У8

2%t

Ckt В

%

2V8

1У8

2У8

1У8

2Ув

1Ув

2%

1Ув

2%

1%

2%

084

Ckt A

%

2V8

1Ув

2Ув

1Уе

2Ув

1У8

2%t

1%

2%t

1Ув

2%t

Ckt В

V8

2Уа

1У8

2Ув

1Ув

2Ув

1Ув

2%

1У8

2%

1Ув

2%

094

Ckt A

%

2V8

1Уб

2Уа

1

Ve

2%t

1Ув

2%t

1%

2%t

1%

ЗУв“

Ckt В

%

2Ve

Ув

2У8

V/a

2Ув

1Ув

2%

1Уа

2%

1Ув

2%

104

Ckt A

%

2Ув

1У8

2Ув

1Ув

2%t

1Уз

2%t

1Ув

2%t

1У8

ЗУв“

Ckt В

%

2Ув

1Уб

2Ув

1Ув

2Уе

1Ув

2%

1%

ЗУв“

1У8

ЗУв“

LEGEND

CV

— Constant Volume

L

— Liquid Line

S

— Suction Line

VAV

— Variable Air Voiume

‘Double suction riser required on units with field installed unloader

on circuit В compressor if condensing unit is elevated above
evaporator.

tDouble suction riser required on units with field installed unloader

on circuit В compressor if condensing unit is elevated above

evaporator.

“Double suction riser required on all unit configurations if condens­

ing unit is elevated above evaporator.

NOTES:

1.

Addition

of

2

unloaders

to

circuit

В

compressor

is

not

recommended

2

38AH094 and 38AH104 piping sizes apply only to factory sup­

plied unit configurations They do NOT take into account any field
installed unloaders

3

Piping sizes are based on unit operation above 40 F (4 4 C) satu­

rated suction temperature (SST) When operating below 40 F

(4 4 C), refer to Carrier System Design Manuai, E20-IÌ piping de­

sign program, or ASHRAE Handbook to select proper line sizes

4

Pipe sizes are based on the total linear length shown for each

column, plus a 50% allowance for fittings.

5

Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop

design criteria may allow selection of smaller pipe sizes, but at a

penalty of decreased system capacity and efficiency

6.

Double suction risers may be required if condensing unit is el­

evated above the evaporator See footnotes and double suction

riser table below

7 Refer to Carrier System Design Manual or to E20-II design

programs for further information on selecting pipe sizes for split
systems

8. All pipe sizes are OD inches Equivalent sizes in millimeters

follow

in.

mm

%

15.9

Уе

22.2

v/a

28.6

V/a

34 9

V/a

41 3

2Уа

54 0

2%

66 7

ЗУв

79 4

3%

92 1

Table 6B — Refrigerant Piping Requirements for Double Suction Risers,

38AH054-104 Duai-Circuit Units — 60 Hz

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)

UNIT 38АН

50-75

75-100

100-150

150-200

15.2-22.9)

(22.9-30.5

30.5-45.7

(45.7-61.0

A

В

С

А

В

С

А

В

С

А

В

С

054

Ckt А

Ckt В

_

___

___

V/a

2Ув

2%

064

Ckt A

Ckt В

_

___

___

___

V/a

2Va

2%

074

Ckt A
Ckt В

_

___

___

1Ув

2Ув

2%

1Ув

2Уа

2%

084

Ckt A
Ckt В

_

1Ув

2Уе

2%

1Уе

2Ув

2%

V/a

2Va

2%

094

Ckt A
Ckt В

1У8

2Ув

2%

V/a

2Ув

2%

1%

2Ув

2%

V/a

2%

ЗУв

104

Ckt A

1Ув

2Ув

2¥а

V/a

2Ув

2%

1Ув

2Ув

2%

V/a

2%

ЗУв

Ckt В

1Ув

2%

ЗУв

V/a

2%

ЗУв

LEGEND

— Not Required

Pipe A

— Suction Riser Without Trap

Pipe B

— Suction Riser With Trap

Pipe C

— Suction Line to Condensing Unit

NOTES.

1 See Refrigerant Piping Requirements table at top of page to de­

termine need for double suction risers.

2 Pipe sizes are based on the total linear length, shown for each

column, plus a 50% allowance for fittings.

Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1 1C) at nominal rating conditions Higher design pressure

drop criteria may allow selection of smaller pipe sizes but at a pen­
alty of decreased system capacity and efficiency.
Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split

systems
All pipe sizes are OD inches. See Table 6A notes for metric

equivalents
Refer to Fig. 13 for double suction riser construction

16