Aim [p ttd – Carrier 38AH044-134 User Manual

Page 36

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

MODUPANEL

POWER
SUPPLY
115-1-60

OR 220-1-50

LI L2

I

^J(23j

ISII221

1211211

11211121M l U l l i

1 + '

^ 1

- V

\

380V, 380/415V,

346V ONLY

FIELD

POWER

,1

I i

NOTES:

1 Factory wiring is in accordance with NEC Fieid modifications or ad­

ditions must be in compiiance with aii appiicabie codes

2 Wiring for fieid power suppiy must be rated 75 C minimum Use cop­

per, copper-ciad aiuminum, or aluminum conductors. Maximum in­
coming wire size for each terminal block is 500 kcmil

3. Terminal blocks TB3 and TBX1 are for external field control con­

nections Control connections are to be class 1 wiring

4 Field-supplied components (IFC, LLS-A1 and A2) must have a maxi­

mum sealed coil rating of 30 va each (0 25 amp at 120 vac,
0.13 amp at 230 vac) AHMS IFC-AUX contact must have minimum

pilot duty rating of 400 va each (3 4 amps at 120 vac, 1.8 amps at

230 vac)

5. Replacement of factory wires must be with type 105 C wire or its

equivalent

6. Field-supplied liquid line solenoid valves installed at the evaporator

are required on all units

7 Units have 175 va of power available for field-installed accessories

"I" I

4-

-F

mi

mm

aim

[p

tTD

11

NEC DiSCONNECT

PARALLEL CONDUCTORS

38AH124,134 {208/230V)

DUAL POINT MAIN POWER ENTRY

NEC DISCONNECT

38AH124,134 {ALL VOLTAGES)

DUAL POINT MAIN POWER ENTRY

LEGEND

AHMS

— Air Handler Motor Starter

SDR —

Solenoid Drop Relay

AUX

— Auxilliary

TB —

Terminal Block

C

— Compressor Contactor

TBX —

Terminal Block for Variable

FU

— Fuse

Air Volume Units

GND

— Equipment Ground

TM —

Timer Motor

IFC

— Indoor Fan Control

TR —

Timer Relay

kcmil

— Thousand Circular Mils

TRAN —

Transformer

LLS

— Liquid Line Solenoid

U —

Unloader Solenoid

NEC

— National Electrical Code

( U S A Standard)

Factory Wiring

Field Wiring

Fig, 28 — Field Wiring, Single ModuPaneF” Control, Units 38AH124 and 134

36

Advertising