Carrier 38AH044-134 User Manual

Page 47

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Fig. 45 — Accumulator and Fusible Plug

Timer Functions — (See Timer Cycle, Fig. 47.) Each
refrigeration circuit is controlled by an independent timer

which allows for the independent operation of each refrig­
eration circuit.

NOTE: Unit 38AH044-084 optional single-circuit units have

one timer which controls the lead compressor. Lag compres­
sor is controlled by CCPS (capacity control pressure switch).

SWITCH A — The timer is energized through contacts A-Al
or A-A2. This establishes the Time Guard® function which
prevents compressor short-cycling. Start of compressor is de-

i

layed approximately 5.5 minutes after shutdown.

^' SWITCH B — The compressor is initially energized through

contacts B-Bl.

SWITCH D — Contacts D-Dl provide a 2*/2-minute bypass
of the low-pressure switch at start-up for winter-start con­
trol. On 38AH044-084 optional single-circuit units, contacts

D-D2 control start-up of compressor A2.

SWITCH E — Contacts E-EI provide a 40-second bypass
of the oil pressure switch at start-up. If oil pressure does not

build to the required minimum pressure in 40 seconds, the

compressor shuts down and the control circuit locks out.

On 38AH044-084 dual-circuit and 38AH094,104 units, lag

circuit B start-up is delayed 60 seconds after a call for cool­
ing is made to the circuit. This prevents compressor(s) in
both lead and lag circuits from starting at the same time.

Control Circuit Reset — The control circuit locks out
if the unit shuts down because of low oil pressure, high dis­
charge gas temperature (DGT), or excessive high-side pres­
sure. To reset the control circuit, open and close the fan cir­
cuit breaker (FCB). This resets the timer, and the unit restarts
under Time Guard control. At start-up, if the low-pressure

switch (EPS) does not close after 2'/2 minutes, the unit shuts

down. When the pressure builds enough for the EPS to cut
in, the control circuit is energized automatically and start-up
proceeds under Time Guard control.

TO PREVENT REFRIGERANT LEAKAGE)

Fig. 46 — Pressure-Actuated Capacity Control Valve

CONTROL

Sequence of Operation — Units are controlled with

electromechanical components. Each refrigeration circuit

(except 38AH044-084 optional single-circuit units) is oper­

ated by an independent timer which controls the operation

sequence of each circuit.

On a call for cooling, first stage cooling thermostat TCI

closes. Condenser fans and timer (TM) are energized. After

approximately 7 seconds, timer contacts E-El close. Ap­
proximately 12 seconds after TCI closes, normally-open timer
contacts B-B1 close for 1 second. This energizes compres­

sor A1 contacts CAl and starts the compressor. At the same

time, solenoid drop relays (SDRs) and liquid line solenoid
valve no. 1 (EES-A for 38AH044-084 dual-circuit units;
EES-Al for all other units) open, and timer relay no. 1 (TR2)

is energized. Normally open TR2 contacts close, completing
a circuit around B-Bl and through compressor A1 contac­
tors to maintain compressor operation when B-Bl contacts
open. Contacts E-El remain closed for approximately 40 sec­
onds to bypass the oil pressure switch (OPS). If oil pressure
is insufScient when contacts E-El open, the compressor stops,
the timer cycles off, and the control circuit locks out. At start­
up, timer contacts D-Dl are closed, bypassing low-pressure
relay contacts EPR-A for 21/2 minutes. This provides a win­

ter start-up feature.

Approximately 2V2 minutes after TCI closes, timer con­

tacts D-Dl open and D-D2 close. If pressure is insufficient
to close the low-pressure switch, the low-pressure switch re­

lay is open, the compressor shuts down, and the Time Guard
control is initiated. (Time Guard control prevents compres­
sor from restarting for 5 minutes after the demand for cool­
ing is satisfied.)

47

Advertising