NOTES:

1

Liquid line soienoid vaive LLS-A is used for solenoid

drop on circuit A. Liquid line solenoid valve LLS-B is

used for solenoid drop for circuit B.

2 Solenoid drop is a safety feature which prevents refrig­

erant migration to the compressor during the OFF cycle.

It is recommended on all systems and required on sys­

tems where piping exceeds 75 ft (22 9 m) in length.

3 The TSR-01 relay pack requires 10 va.
4

Factory wiring is in accordance with NEC; field modi­

fications or additions must be in compliance with all ap­

plicable codes.

5

Wiring for field power supply must be rated 75 0 mini­

mum. Use copper, copper-clad aluminum, or alumi­
num conductors. Maximum incoming wire size for each

ferminal block is 500 kcmil.

6 Terminal blocks TB3 and TB4 are for external field con­

trol connections Control connections are to be class 1

wiring

10

Field-supplied components (IFC, LLS-A, and LLS-B) must

have a maximum sealed coil rating of 30 va each (0.25

amp at 120 vac and 0 13 amp at 230 vac) Thermo­
stats must have a minimum pilot duty rating of 300 va

(2 5 amps at 120 vac and 1 3 amps at 230 vac)

Replacement of factory wires must be with type 105 C

wire or its equivalent

Field-supplied liquid line solenoid valves installed at the
evaporator are required on all units

Units have 175 va of power available for field-installed

accessories

To minimize voltage drop, the following wire sizes are

recommended:

LENGTH —

Ft(M)

INSULATED WIRE — AWG

(35 C Minimum)

Up to 50
(15.2)

No 18

50-75
(15.2-22.9)

No 16

More Than 75
(22.9)

No 14

LEGEND

AWG

— American Wire Gage

C

— Compressor Contactor

CR

— Control Relay

HD

— Heating Device

IFC

— Indoor-Fan Contactor

IFR

— Indoor-Fan Relay

kcmil

— Thousand Circular Mils

LLS

— Liquid Line Solenoid

NEC

— National Electrical Code

(US.A Standard)

R

— Heating Relay (field-

supplied 24-v sealed coil,

10 va maximum rating)

RV

— Reversing Valve

SDR

— Solenoid Drop Relay

TB

— Terminal Block

TR

— Timer Relay

Factory Wiring

________Field Wiring

Fig. 20 — Field Wiring, One 2-Stage Thermostat — 38AH044-084 Duai-Circuit Units

28