Table 10B — Electrical Data — 50/60 Hz (38AH044-084 Optional Single-Circuit Units)

OPTIONAL SINGLE-CIRCUIT UNIT

38AH

Voltage

Compressor

A 1 / A O

Nameplate

Supply Voltage

MOCP

ICF

A1

A2

Designation

Model No.

V-Ph-Hz

Min

Max

RLA

LRA

RLA

LRA

500

208/230-3-60

187

254

179 4

225

434 7

67 9

345

67 9

345

600

460-3-60

414

508

91 3

100

2186

34 6

173

34.6

173

100

575-3-60

518

632

78.4

100

162 4

28.8

120

28.8

120

044

200

06E4250/250

380-3-60

342

418

93.5

125

241.2

34 6

191

34 6

191

800 (PW)

230-3-50

198

254

180.2

225

296 7

67 9

207

67.9

207

900

380/415-3-50

342

440

91.5

100

2196

34 6

173

34.6

173

300 (PW)

346-3-50

325

367

100.0

125

165 9

33 3

115

33 3

115

500

208/230-3-60

187

254

206.6

250

535 7

89.7

446

67 9

345

600

460-3-60

414

508

102 4

125

268 6

43.6

223

34.6

173

054

100

06E4265/250

575-3-60

518

632

88 0

125

206 4

36 5

164

28.8

120

200

380-3-60

342

418

107 1

150

297 2

45.5

247

34.6

191

900

380/415-3-50

342

440

102 7

125

269 6

43 6

223

34 6

173

300 (PW)

346-3-50

325

367

107 0

150

198.9

44.9

148

33 3

115

500

208/230-3-60

187

254

249 3

350

6175

106 4

506

89 7

446

600

460-3-60

414

508

115.5

150

307 6

46 8

253

43.6

223

100

575-3-60

518

632

100 6

125

226 1

40.4

176

36.5

164

200

380-3-60

342

418

126 9

175

341 1

52.6

280

45 5

247

900

380/415-3-50

342

440

115 7

150

335 6

46 8

280

43 6

223

300 (PW)

346-3-50

325

367

129 8

175

230 5

53.8

168

44.9

148

500

208/230-3-60

187

254

330 5

450

829.0

147 4

690

106 4

506

600

460-3-60

414

508

148 6

200

408 2

65 4

345

46.8

253

0 7 4

100

06E8299/275

575-3-60

518

632

132 2

175

336 8

57.1

276

40.4

176

200

380-3-60

342

418

174.5

250

458 0

78.8

382

52 6

280

900

380/415-3-50

342

440

143 0

200

403 8

65.4

345

46 8

280

300 (PW)

346-3-50

325

367

170 8

250

300 4

79.5

229

53.8

168

500

208/230-3-60

187

254

371.5

500

870.0

147 4

690

147 4

690

600

460-3-60

414

508

167 2

225

426.8

65.4

345

65.4

345

084

100

06E8299/299

575-3-60

518

632

148.9

200

353 5

57.1

276

57 1

276

200

380-3-60

342

418

200 7

250

484.2

78 8

382

78 8

382

900

380/415-3-50

342

440

167 6

225

428 4

65 4

345

65 4

345

300 (PW)

346-3-50

325

367

205 3

250

334.9

79 5

229

79.5

229

COMPRESSOR*

LEGEND

FLA

— Full Load Amps

ICF

— Maximum Instantaneous Current Flow During Starting. (The

point in the starting sequence where the sum of the LRA

for the starting compressors, plus the total RLAforall run­

ning compressors, plus the FLA for all running fan mo­

tors is maximum)

kcmil

— Thousand Circular Mils

LRA

— Locked Rotor Amps

Max

— Maximum

MCA

— Minimum Circuit Amps (used for sizing; complies with Na­

tional Electrical Code [NEC] [ U S A Standard],

section 430-24)

Min

— Minimum

MOCP

— Maximum Overcurrent Protection (used for sizing dis­

connect, complies with NEC Article 440, Section 22).

RLA

— Rated Load Amps

PW

— Part Wind Only

*AII compressors are across-the-line start only except 38AH044

230

V,

3-phase, 50 Hz; and all 346 v, 3-phase, 50 Hz

tUnits are suitable for use on electrical systems where voltage sup­

plied to unit terminals is within listed minimum to maximum limits

NOTES'
1 Maximum allowable phase imbalance voltage - 2%; amps -10%

2 Maximum incoming wire size for terminal block is 500 kcmil

24