NOTES;

1 Liquid iine soienoid vaives LLS-A1 and A2 are used tor

soienoid drops

2

Solenoid drop is a safety feature which prevents refrig­

erant migration to the compressor during the OFF cycle

It is recommended on all systems and required on sys­

tems where piping exceeds 75 ft (22 9 m) in length

3 The TSR-01 relay pack requires 10 va.
4

Factory wiring is in accordance with NEC; field modi­

fications or additions must be in compliance with all ap­

plicable codes

5. Wiring for field power supply must be rated 75 C mini­

mum Use copper, copper-clad aluminum, or alumi­
num conductors Maximum incoming wire size for each

terminal block is 500 kcmil

6 Terminal blocks are for external field control connec­

tions Control connections are to be class 1 wiring

10

Field-supplied

components

(IFC,

LLS-A1,

and

LLS-A2) must have a maximum sealed coil rating of
30 va each (0 25 amp at 120 vac and 0 13 amp at

230 vac) Thermostats must have a minimum pilot duty

rating of 300 va (2 5 amps at 120 vac and 1.3 amps at

230 vac)

Replacement of factory wires must be with type 105 C

wire or its equivalent

Field-supplied liquid line solenoid valves installed at the

evaporator are required on all units

Units have 175 va of power available for field-installed

accessories

To minimize voltage drop, the following wire sizes are

recommended:

LENGTH —

Ft(M)

INSULATED WIRE — AWG

(35 C Minimum)

Up to 50

(15.2)

No 18

50-75

(15.2-22.9)

No 16

More Than 75

(22.9)

No 14

LEGEND

AWG

— American Wire Gage

C

— Compressor Contactor

CCPS

— Capacity Control Pressure

Switch

CR

— Control Relay

HD

— Heating Device

IFC

— Indoor-Fan Contactor

IFR

— Indoor-Fan Relay

kcmil

— Thousand Circular Mils

LLS

— Liquid Line Solenoid

NEC

— National Electrical Code

(U S.A Standard)

R

— Heating Relay (field-

supplied 24-v sealed coil,

10 va maximum rafing)

RV

— Reversing Valve

SDR

— Solenoid Drop Relay

TB

— Terminal Block

TR

— Timer Relay

Factory Wiring

------------- Field Wiring

Fig. 21 — Field Wiring, One 2-Stage Thermostat — 38AH044-084 Optionai Single-Circuit Units