ooooooO O O O O

o

OOOO

VIEW 5-5

TOP VIEW OF CONTROL BOX SHELF

WITH FIELD POWER SUPPLY CONNECTIONS

RELIEF VALVES LOCATED ON

COMPRESSORS A2 AND B1 ARE EQUIPPED

WITH A 3/8' SAE FLARE FOR

FIELD CONNECTION

SCALE 1:8

(8) MTG HOLES

7/32' DIA

7'-11 9/16'

[2‘128mmD

-7 -4 11/16'-

[2252m(T)

HTG HOLES

-7'-7 11/16'-

C2326n<r[i}

BASE OVERALL

RIGHT-END VIEW

Chart 1, Field Power Supply Connections

UNIT

38AH

VOLTAGE

Hz

DIAMETER — in. (mm)

QUANTITY

208/230

60

3% (92)

2

094

460, 575,

380

60

3% (92)

1

346, 380/415

50

35/8

(92)

1

LEGEND

C

— Copper Fin Coils

MTG

— Mounting

SAE

— Society of Automotive Engineers

NOTES:
1 The approximate operating weight of the unit is:

38AH-094—

5088 lb (2308 kg)

38AH-094-C

5813 lb (2637 kg)

2 Unit must have clearances for airflow as follows:

Top — Do not restrict in any way

Ends — 5 ft [1524 mm]
Sides — 6 ft [1829 mm]

3 Mounting holes may be used to mount unit to concrete pad They are not

recommended for mounting unit to spring isolators

4 Two 3%" (92-mm) dia holes are recommended for parallel conductors on

208/230

V

units.

5. Circled numerals in Top View refer to condenser fans by position
6 If spring isolators are used, a perimeter support channel between the unit

and the isolators is recommended

7. See Table 1 for rigging center of gravity (Dimensions X,Y) See Table 2A

and 2B for A-D corner weights

Fig. 3 — Dimensions — Unit 38AH094