Carrier 38AH044-134 User Manual

Page 19

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 9A — Refrigerant Piping Requirements for 38AH044-084 Optionai Singie-Circuit Units and

38AH124,134 Modular Units (Duai Circuit) — 50 Hz

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)

UNIT

38AH

15-20

(4.6-6.1)

20-50

(6.1-15.2)

50-75

(15.2-22.9)

75-100

(22.9-30.5)

100-150

(30.5-45.7)

150-200

(45.7-61.0)

L

s

L

s

L

s

L

s

L

s

L

S

044

%

2У8

Ve

2У8

1У8

2Уа

1Уа

2%*

1У8

2%*

1%

2%*

054

%

2Ve

V/8

2Уа

1У8

2%*

1Уа

2%*

1Уа

2%*

1%

ЗУа*

064;

Modules 124A,

124B,134A

%

2Va

V/a

2%t

1У8

2%t

1Уб

2%-f

1%

ЗУа*

1%

ЗУа*

074;

Module 134B

%

2Ув

tVa

2%t

1У8

2%t

13/a

ЗУ8*

1%

ЗУе*

1%

ЗУа*

084

IVe

2У8

V/a

25/st

1%

ЗУа*

1%

ЗУа*

1%

ЗУа*

1%

3%*

LEGEND

CV

— Constant Volume

L

— Liquid Line

S

— Suction Line

VAV

— Variable Air Volume

‘Double suction riser required on all units configurations if condens­

ing unit is elevated above evaporator.

tDouble suction riser required on units with factory installed VAV op­

tion or CV units with additionai field installed unloader on circuit A1

(lead) compressor if condensing unit is elevated above evaporator

NOTES'

1; Addition of field-installed unloaders on A2 (lag) compressor is not

recommended

2

Piping sizes are based on unit operation above 40 F (4 4 C) satu­

rated suction temperature (SST) When operating below 40 F

(4 4 C), refer to Carrier System Design Manual, E20-II piping de­
sign program, or ASHRAE Handbook to select proper line sizes

3

Pipe sizes are based on the total linear length shown for each

column, plus a 50% allowance for fittings

4

Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1.1 C) at nominal rating conditions Higher pressure drop

design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency

Double suction risers may be required if condensing unit is el­

evated above the evaporator See footnotes and double suction

riser table below.

Refer to Carrier System Design Manual, E20-II design program,

or ASHRAE Handbook for further information on selecting pipe

sizes for split systems.
All pipe sizes are CD inches Equivaient sizes in millimeters
follow:

in.

mm

%

15.9

Ve

22 2

1Уа

28 6

1%

34 9

1%

41 3

2У8

54 0

2%

66.7

ЗУа

79 4

ЗУа

92 1

Table 9B — Refrigerant Piping Requirements for Doubie Suction Risers,

38AH044-084 Optional Single-Circuit Units and 38AH124,134 Modular Units (Dual Circuit) — 50 Hz

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)

UNIT

38AH

15-20

(4.6-6.1)

20-50

(6.1-15.2)

50-75

(15.2-22.9)

75-100

(22.9-30.5)

100-150

(30.5-45.7)

150-200

(45.7-61.0)

A

В

c

A

В

С

А

В

С

А

В

С

А

В

С

А

В

С

044

1%

2Уа

25/8

15/8

25/а

25/а

15/8

25/8

25/8

054

1%

2Уа

2%

1%

2Уа

25/8

15/8

2У8

25/8

15/8

25/а

ЗУа

064;

Modules 124A,

124B, 134A

1%

2Уа

2%

1%

2Уа

2%

1%

2Уа

25/8

15/8

25/8

ЗУе

15/8

25/а

ЗУа

074;

Module 134B

1%

2Уа

2Уа

1%

2Уа

2%

1%

25/8

ЗУ8

15/8

25/8

ЗУа

15/8

ЗУа

35/а

084

1Уа

2Уа

2%

1%

2%

ЗУа

1%

25/8

ЗУа

15/8

25/а

ЗУа

15/8

ЗУа

35/8

LEGEND

— Not Required

Pipe A

— Suction Riser Without Trap

Pipe B

— Suction Riser With Trap

Pipe C

— Suction Line to Condensing Unit

NOTES.

1. See Refrigerant Piping Requirements table at top of page to de­

termine need for double suction risers

2. Pipe sizes are based on the total linear length, shown for each

column, plus a 50% allowance for fittings

3

Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1 1C) at nominal rating conditions Higher design pressure
drop criteria may allow selection of smaller pipe sizes but at a pen­
alty of decreased system capacity and efficiency

4.

Refer to Carrier System Design Manual or to E20-II design

programs for further information on selecting pipe sizes for split
systems

5

All pipe sizes are CD inches See Table 9A notes for metric

equivalents

6 Refer to Fig 13 for double suction riser construction

19

Advertising