38ан124,134, A caution, Caution – Carrier 38AH044-134 User Manual

Page 31: Lb2j

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

38АН124,134

MODULE

124А OR 134A

ТВЗ

Ф

TIME

GUARD®
CONTROL

SDR2 ^

CCPS -ÆA^

MODULE

124B OR 134B

ACCESSORY

RELAY
PACKAGE

CR1

—^—II—vio

CR2

TB3

TIME

GUARD®
CONTROL

SDR2 ^

—It—^

CCPS

SDR2

;cAi

'CA2]

SDR2

|] Щ И

L

j

U_SEE

NOTE 2

_____ I

|T

ls

1

I

T

lls

I

LB2j

I___ I

-

yel

A

CAUTION

Internal TSR-01 relay contacts are rated for 1 amp/24 vac.

q

-COMMUNICATION

OUT

- COMMUNICATION IN

CARRIER COMMUNICATING
TEMP MONITOR THERMOSTAT

.(MODEL MS(T)01ES)

++-WHtTE--

e

«ED— e

BLUE— e

____YELLOW- e

-- - — OREEN-- <D

REMOTE ROOM

TEMP SENSOR

•Jumper removed only when separate 24-v transformer power

source is used to power the TSR-01 relay pack

TSR-01 RELAY PACK CIRCUIT BOARD

-----------

fan

"I

1

HEAT 2 -i

-------- HEAT 1 -5

0

'■--------- COOL2-------------‘ I

------- COOL1---------------- '

" —"________ J

I —24 VAC (R)

24 VAC (Comrtran)

NOTES:

1 Liquid line solenoid valves LLS-A1 and A2 are used for

solenoid drop on Module 124A or 134Aon circuit A Liq­
uid line solenoid valves LLS-B1 and B2 are used for

solenoid drop for Module 124B or 134B. Solenoid drop

is a safety feature which prevents refrigerant migration

to the compressor during the OFF cycle It is recom­

mended on all systems and required on systems where
piping exceeds 75 ft (22 9 m) in length

2

Disconnect black wire from CR2 terminal 6; cap loose

end and secure Connect new field-supplied wire from

CR2 terminal 6 to ТВЗ terminal 1 on module 124B or

134B

3 The TSR-01 relay pack requires 10 va
4

Factory wiring is in accordance with NEC; field modi­

fications or additions must be in compliance with all ap­
plicable codes

5 Wiring for field power supply must be rated 75 C mini­

mum Use copper, copper-clad aluminum, or alumi­

num conductors Maximum incoming wire size for each
terminal block is 500 kcmil.

6. Terminal blocks (ТВЗ) are for external field control con­

nections Control connections must be class 1 wiring

10

Field-supplied

components

{IFC,

LLS-A1,A2,

and

LLS-B1 ,B2) must have a maximum sealed coil rating
of 30 va each (0 25 amp at 120 vac and 0 13 amp at

230 vac) Thermostats must have a minimum pilot cluty

rating of 300 va (2 5 amps at 120 vac)
Replacement of factory wires must be with type 105 C

wire or its equivalent.
Field-supplied liquid line solenoid valves installed at the
evaporator are required on all units

Units have 175 va of power available for field-installed

accessories.

To minimize voltage drop, the following wire sizes are

recommended:

LENGTH —

Ft(M)

INSULATED WIRE — AWG

(35 C Minimum)

Up to 50

(15.2)

No 18

50-75
(15.2-22.9)

No 16

More Than 75
(22.9)

No 14

LEGEND

AWG

— American Wire Gage

C

— Compressor Contactor

CCPS

— Capacity Control Pressure

Switch

CR

— Control Relay

HD

— Heating Device

IFC

— Indoor-Fan Contactor

IFR

— Indoor-Fan Relay

kcmil

— Thousand Circular Mils

LLS

— Liquid Line Solenoid

NEC

— National Electrical Code

(U S.A Standard)

R

— Heating Relay (field-

supplied 24-v sealed coil,

10 va maximum rating)

RV

— Reversing Valve

SDR

— Solenoid Drop Relay

TB

— Terminal Block

TR

— Timer Relay

Factory Wiring

------------- Field Wiring

Fig. 23 — Field Wiring, One 2-Stage Thermostat — Units 38AH124 and 134

31