38AH094,104

TBS

TIME
GUARD®

CONTROL

SDR2

>—ih—ox°-

CCPS

SDR2

(PAU

0 H]

0 ¿HI]

TB4

0

ACCESSORY

RELAY
PACKAGE

CR1

I r

I I

I I
I !

0—

[4]--------- 0^.

iLLSl

L

bij

J

LI

+-

L2

A

CAUTION

Internal TSR-01 relay contacts are rated for 1 amp/24 vac.

— — — — = = — — — —

- COMMUNICATION OUT

- COMMUNICATION IN

CARRIER COMMUNICATING

TEMP MONITOR THERMOSTAT

.(MODEL MS(T)01ES)

---------- WHITE-

-

-----RED —

--BLUE-

.+ -YEUDW.

— GREEN -

REMOTE ROOM

TEMP SENSOR

*To control heating device and provide automatic indoor-

fan operation on heating.

fJumper removed only when separate 24-v transformer power

source is used to power the TSR-01 relay pack

NOTES:

1

Liquid line solenoid valve LLS-A1 is used for solenoid

drop on circuit A Liquid line solenoid valve LLS-B1 is

used for solenoid drop for circuit B.

2

Solenoid drop is a safety feature which prevents refrig­

erant migration to the compressor during the OFF cycle.
It is recommended on all systems and required on sys­
tems where piping exceeds 75 ft (22 9 m) in length

3 The TSR-01 relay pack requires 10 va.
4

Factory wiring is in accordance with NEC; field modi­

fications or additions must be in compliance with all ap­

plicable codes

5

Wiring for field power supply must be rated 75 C mini­

mum Use copper, copper-clad aluminum, or alumi­
num conductors. Maximum incoming wire size for each

terminal block is 500 kcmil

6

Terminal blocks are for external field control connec­

tions Control connections must be class 1 wiring

7

Field-supplied

components

(IFC,

LLS-A1,

and

LLS-B1) must have a maximum sealed coil rating of
30 va each (0 25 amp at 120 vac and 0 13 amp at
230 vac) Thermostats must have a minimum pilot duty

rating as follows:

----------

fan

1

------ COOL

-24 VAC (R)

-24 VAC (Common)----------- 1

TSR-01 RELAY PACK CIRCUIT BOARD

8 Replacement of factory wires must be with type 105 C

wire or its equivalent

9 Field-supplied liquid line solenoid valves installed at the

evaporator are required on all units

10

Units 38AH094 has 140 va and unit 38AH104

has 130 va of power available for field-installed

accessories

11

To minimize voltage drop, the following wire sizes are

recommended:

38AH

VA

(Ea Stage)

AMPS

VAC

094

275

2.29

120

1 15

240

104

325

2 70

120

1 35

240

LENGTH —

Ft(M)

INSULATED WIRE — AWG

(35 C Minimum)

Up to 50

(15.2)

No. 18

50-75
(15.2-22.9)

No 16

More Than 75
(22.9)

No 14

LEGEND

AWG

— American Wire Gage

C

— Compressor Contactor

CCPS

— Capacity Control Pressure

Switch

CR

— Control Relay

HD

— Heating Device

IFC

— Indoor-Fan Contactor

IFR

— Indoor-Fan Relay

kcmil

— Thousand Circular Mils

LLS

— Liquid Line Solenoid

NEC

— National Electrical Code

(U S.A Standard)

R

— Heating Relay (field-

supplied 24-v sealed coil,

10 va maximum rating)

RV

— Reversing Valve

SDR

— Solenoid Drop Relay

TB

— Terminal Block

TR

— Timer Relay

Factory Wiring

------------- Field Wiring

Fig. 22 — Field Wiring, One 2-Stage Thermostat — Units 38AH094 and 104