6. If the event is to occur sometime before or after sunrise or sundown, enter that period of time in

the Offset box. To schedule an event to occur before sunrise or sundown, enter a negative value;
to schedule an event to occur after these times, enter a positive value. For example, if you want an
ON event to occur 30 minutes after sundown, enter 00:30. If you want a DIMMING event to
occur 15 minutes before sunrise, enter -00:15.

7. In the Value box, do one of the following:

• Select the preset to be used to update the values of all the data points added to the Scheduler

that have that preset defined for them. Alternatively, you can enter a new preset and then go
back to the Scheduler: Data Points Web page and define the value (or values) for the preset.

• Enter a valid value to be written to all the data points. To enter a value, all the data points

added to the Scheduler must have the same network variable type (e.g., SNVT_switch).

8. In the Priority box, enter a priority for the event between 0 to 255 (highest to lowest priority).

This priority essentially locks out events with lower priorities so that they cannot update the data
points written to by this event. Once the Scheduler executes the event, the data points can only be
updated by an event that has an equal or higher priority.

9. To create additional events in the exception, right-click anywhere in the Time or Value boxes, and

then click Add in the shortcut menu. A new row for the event is added to the dialog. Repeat steps
4–7 to specify the Time and Value of the new event in the exception. You can create up to one
event per minute.