CIRCUTOR AR5L Series User Manual

Page 36

Advertising
background image

36

- TIME OFF: When selecting this option the present OFF conditions are shown

on display; and the procedure is equal to the above one.

TIME .OFF
00 /00 /00 00 :00 : 00

day/month/year hour:minute:second

POINTS TO CONSIDER:

a) To void the time TRIGGER, all values must be zero.

b) If only the ON & OFF TIME are programmed (two DATES set to zero),

the defined time period will be cyclically repeated by the analyzer.

ADDITIONAL NOTES:

a) The analyzer will save data in memory only when both TRIGGER

conditions are met: Time (ON-OFF) and Parameter (maximum and
minimum). If any condition is not met, no value is stored to memory
(STORE OFF state). In case that trigger conditions are void (ON & OFF set
to zero, and parameter set to AUTO), all values will be saved in memory
according to the previously defined recording period.

b) If trigger conditions are met at any moment within the defined recording

period, the average values for the whole period will be saved in memory.