8.- TECHNICAL SPECIFICATIONS

Supply voltage:
Through an external power supplier set 100 V a.c. – 240 V a.c.
Battery: 5VHAA 1200 (Ni-MH)
Frequency : 50...60 Hz
Burden : 15 VA
Operation temperature : 0 / 40 ºC
Altitude:

≤ 2000

Maximum relative humidity 85 % (no condensation)
Measuring circuit : Three (3 or 4 wires), ARON, single-phase and bi-phase

Safety : Category III - 600 V, as per EN 61010
Pollution degree 2
Indoor use
Voltage measurement:
Measuring range : 20 to 500 V a.c. (phase-neutral) CAT III
automatic scale adjustment
Other voltages : through suitable voltage transformers
Frequency : 45 to 65 Hz

Current measurement:
Measuring range: see available current clamps
Current transducer ratio : user-programmable
Measurement units : automatic scale adjustment

Built-in clock with rechargeable battery: Date and time

Display : LCD; 160 x 160 pixels

(Back-light)

RS-232 output : serial type output
Internal memory : 1 Mb

Accuracy class:

Voltage ..................................... 0.5 % of readout

± 2 digits

Current ..................................... 0.5 % of readout

± 2 digits

Active power ............................. 1.0 % of readout

± 2 digits

Reactive power.......................... 1.0 % of readout

± 2 digits


Measuring conditions to assure accuracy class:
- Errors due to voltage and current transformer not included
- Temperature range : 5 ºC to 45 ºC
- Power factor : 0.5 to 1
- Measuring range : between 5 % and 100 %

MECHANICAL CHARACTERISTICS

Case : Portable case.
Dimensions : 220 x 60 x 130 mm

Connection terminals : input/output terminals
Keyboard/ display : in frontal panel
Weight: 0,8 kg.

Advertising