6.1.2.4.- PARAM: Choosing the parameters to be saved

As said before, parameters to be saved in memory are user-definable when

working with STD files.

Pressing [ENTER] previously user-defined parameters are automatically

validated.

- To modify:

Place over the desired parameter with keys [

6

6

6

6], [5

5

5

5], [8

8

8

8] or [3

3

3

3].

Pressing [SET] the state of the parameter switches. Parameters to be

saved are on a black background, and the ones to be not save are on a
white background.

Placing over the text Inst (Instantaneous values) and pressing [SET], you

can now select the maximum values to be saved (MAX).

Placing over the text Max (Maximum values) and pressing [SET], you can

now select the minimum values to be saved (MIN).

Placing over the text MIN (Minimum values) and pressing [SET],you can

now select the parameters of harmonics that will be kept. Including the
number of harmonics(30 or 50), V and I for each phase and neutral current
(only in AR5-L model)

Press [ENTER] to validate the choice or [ESC] to exit with no modification.

Note:

- In case that have been selected some not-compatible parameters with the

active measuring circuit, when exiting Setup, analyzer will warn the user
about this fact and will automatically unselect such wrong parameters.

- If values the parameters to be stored are changed, when exiting setting

actions, the display will show:

“Error: New file should be created”

This message is shown since the change of parameters in an already existing file

is not allowed. Follow these instructions to change the parameters of a file:

1. If you want to keep the file name.

• Stop analyzer data recording process: SET -> RUN -> Stop.
• Exit SETUP.
• Delete the existing file: SET -> FILES -> DELETE.
• Modify the parameters to be saved: SET -> RECORD -> PARAM
• Enable the analyzer data recording process: SET -> RUN -> Run
• Exit SETUP.

2. If you want to change the file name.

• Change the file name: SET -> RECORD -> NAME.
• Modify the parameters to be saved: SET -> RECORD -> PARAM
• Exit SETUP.