CIRCUTOR DHB Series User Manual

Page 24

Advertising
background image

24

Table 5

ALr1, ALr2, ALr3, ALr4

Parameter

symbol

Description

Range of changes

P_A1
P_A2
P_A3
P_A4

Input quantity, steering the alarm.

InP1 – Main input (indicated

value).
InP2 – input of the auxillary

counter.

PrL1
PrL2
PrL3
PrL4

Alarm lower threshold.

-19999...99999

PrH1
PrH2
PrH3
PrH4

Alarm upper threshold.

-19999...99999

tYP1
tYP2
tYP3
tYP4

Alarm type. Fig. 12 presents the
graphical imaging of alarm types

n-on – normal (transition from

0 to 1),
n-oFF – normal (transition

from 1 to 0),
on - switched on,
oFF – switched off,
H-on – manually switched

on; till the change time of the
alarm type, the alarm output
remains switched on for good
H-oFF – manually switched

off; till the change time of
the alarm type the output
alarm remains switched off
for good.