Auto1 – the maximum time interval between pulses for minimum flow

- 16 [s];
-

FUnCt – mathematical functions - for frequency measurement should

be set to

oFF;

-

Cnt1 – set to value 1 (averaging current measurements every second).

Then set the individual characteristics:
-

IndCp – set 2 points;

-

X1 – set – 0 [Hz], Y1 set the corresponding flow 0 m

3

/h;

-

X2 – set 1 pulse – 1 [Hz], Y2 set the corresponding flow 3600 m

3

/h.

Example 2 Programming the analog output: if you want to program the
analog output as a signal 4...20 mA proportional to flow: 4 mA - 0 m

3

/ h,

20 mA - 125 m

3

/h, set the output parameters as follows:

-

P_An – set InP1;

-

AnL set the value 0;

-

AnH set the value 125;

-

typA set the type 4_20A (4..20mA).

Example 3 Programming the alarm output working with time delay:
if we want the alarm 1 to work in the range of flow from 1 m

3

/h

to 30 m

3

/h and to be activated after 10 seconds, set the alarm parame-

ters as follows:
-

P_A1 – set InP1;

-

PrL1- set the value 1;

-

PrH1 -set the value 30;

-

typ1 -set the type on;

-

dLY1- set the value 10;

-

LEd1 – if an alarm indication is needed, it should be set to on, otherwise to oFF.