9. PROGRAMMING EXAMPLES

Example 1. Programming the meter to work with the flowmeter with reed
relay output of the following parameters:
- pulse constant 1K - 4,3956 dm

3

/pulse = 0,0043956 m

3

/pulse;

- minimal flow Q

min

– 0,02 m

3

/h

The parameters of input 1 should be set as follows:
-

tYP1 should be set to FreqL (frequency for (f<10kHz));

The pulse constant for scaling should be given in m

3

, but only five

significant digits can be set. When multiplying by a constant (

SCAL set

to

AND), when rounded to five digits we get value 0.0044 (introducing to

the result of the calculation error of 0.1%). To reduce the error introdu-
ced by the conversion, change the scaling by a constant dividing (

SCAL

set to

div) and as a constant value write the multiplicative inverse:

ConS1= =227,5002275

≈ 227,50

When the inverse is rounded to five digits, the error introduced into the
calculations is of the size of 0.0001%.
-

SCAL1 should be set to dIv, ConS1 should be set to 227,50;

-

t_L1 and t_H1 should be set to a value 10 [ms] (due to the multiplication

of the pulse with a mechanical switch);
-

E-In1 – if no control inputs are used, should be set to bUt;

To set the time, after which a zero flow will be indicated, the maximum time
interval between pulses should be calculated for minimum flow Q

min

.

maximal time interval between pulses t_

max

=

t_

max

=

1

0,0043956

pulse weight [m

3

] * 3600 [s]

Q

min

[m

3

]

0,0043956

*

3600 [s]

6