Installation, Rear vent configuration with vertical termination, For qualified installers only) – Avalon Firestyles Cypress User Manual

Page 19

Advertising
background image

Installation

(for qualified installers only)

19

© Travis Industries

4121130

100-01311

Rear Vent Configuration with Vertical Termination

Use the rear vent conversion from
Travis Industries (SKU 94400998).

Use 8” Diameter Vent

Horizontal sections require a ¼”
(6mm) rise every 12” (305mm) of
travel.

A maximum of three (3) 45° or 90°
elbows may be used. Of these
elbows, only one (1) may be a
horizontal elbow (see illustration).

The termination must fall within the
shaded area shown in the chart.
Use the indicated restrictor position.
NOTE: Restrictor positions are
based upon lab tests. The ideal
restrictor position may vary slightly,
especially when the termination is
near a demarcation line

Horizontal elbows are elbows placed between

two horizontal sections of pipe. One 45° or 90°

horizontal elbow is allowed for this configuration.

Horizontal Elbow

Exhaust Restrictor Position #4

Exhaust Restrictor Extender Installed

0 feet

5 feet (1.5m)

10 feet (3m)

15 feet (4.5m)

20 feet (6m)

25 feet (7.5m)

30 feet (9m)

5 feet (1.5m)

0 feet

0 feet

3' max. (1m)

10 feet (3m)

15 feet (4.5m)

20 feet (6m)

25 feet (7.5m)

30 feet (9m)

0 feet

31' max (9.3m)

3' max. (1m)

31' max (9.3m)

Exhaust Restrictor Position #3

Exhaust Restrictor Extender Installed