100-01410

Mantel Requirements

 Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured

from the non-combustible facing) must fall within the shaded portion of the table.

 Any material above the fireplace that protrudes more than 3/4” (19mm) from the non-combustible

facing is considered a mantel and must meet the mantel requirements.

Mantel Column Clearances

 Combustible mantel columns (legs) that protrude more than ¾” (19mm) from the glass frame

require a 5” (127mm) clearance to the side of the fireplace.

 Combustible mantel columns (legs) that protrude ¾” (19mm) or less from the glass frame must

meet the facing clearances (minimum 2-1/4” (57mm) clearance to the side of the glass frame).

 Non-combustible mantel columns do not have a minimum clearance.

Maximum Mantel Depth (b)

Mantel

Height

Above

Base (a)

52-3/4" (1340mm)

0" (0mm)

1" (25mm)

2" (51mm)

8" (203mm)

7" (178mm)

6" (152mm)

5" (127mm)

4" (102mm)

3" (76mm)

9" (229mm)

10" (254mm)

11" (279mm)

12" (305mm)

51-3/4" (1314mm)

50-3/4" (1289mm)

49-3/4" (1264mm)

48-3/4" (1238mm)

47-3/4" (1213mm)

46-3/4" (1187mm)

53-3/4" (1365mm)