Installation

(For Qualified Installers Only)

© Travis Industries

4141230

100-01270

Pellet Vent Type

 Must be 3" (76mm) or 4” (102mm) diameter Type "L" (except for masonry fireplace installations) -

or - connect the vent to a factory built type "A" chimney. All vent joints (including adapters,
elbows, etc.) must be sealed (typically 500° F. RTV silicone is used).

Installing the Pellet Vent



 Horizontal sections must have a 1/4" (6.4mm) rise every 12" (305mm) of travel.
 Pellet vent connections must be sealed airtight with 500° F. RTV silicone and screwed together

with at least 3 sheet metal screws (unless the vent manufacturer’s requirements specify
otherwise).

Pellet Vent Termination

 Vent must terminate on the exterior of the dwelling. Horizontal terminations must protrude a

minimum of 12" (305mm) from the wall. Vertical terminations must protrude a minimum 24"
(610mm) from the roof surface. In addition, all clearances listed below must be met.

 Must have an approved cap (to prevent water from entering) or a 45° downturn with rodent

screen.

 If the termination is located on a windy side of the house, an approved house shield is

recommended to prevent soot from building up on the side of the house.

 Must not be located where it will become plugged by snow or other material.

A Minimum 4' (1220mm) clearance below or beside any door or window that opens.

(This clearance may be reduced to18” if using outside air (see page 13) – we recommend
the door or window be kept closed during operation.
Minimum 1’ (458mm) clearance below or beside any window that does not open.

B

Minimum 1' (458mm) clearance above any door or window that opens

C

Minimum 2' (610mm) clearance from any adjacent building

D

Minimum 7' (2.134 M) clearance above any grade when adjacent to public walkways

NOTE: Vent may not terminate in covered walkway or breezeway.

E

Minimum 2' (610mm) clearance above any grass, plants, or other combustible materials

F

Minimum 3' (915mm) clearance from any forced air intake of any other appliance

G

Minimum 2' (610mm) clearance below eaves or overhangs

H

Minimum 1' (458mm) clearance horizontally from combustible wall

X

Must be a minimum of 2' (610mm) above the roof

Seal each vent section (including
adapters, elbows, etc...) by
injecting a liberal amount of 500°
F. RTV silicone into the gap
between sections.

500° F. RTV

Silicone

H

G

A

D

F

NOTE: Measure clearances to the nearest edge of the exhaust hood.

A

E

B

C

F

X

H

Install the vent at the clearance specified by the
vent manufacturer.