Mobile Home Requirements

 Outside air is required (used for combustion) - see the directions below.
 The heater must be bolted to the floor (Some states do not require this; check with your local building

department).

 The heater must be grounded to the steel chassis of the mobile home (Some states do not require this;

check with your local building department).

DO NOT INSTALL IN SLEEPING ROOM.

CAUTION:

THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.

Outside Air (Used for Combustion

Use Part #99200136)

Travis Industries strongly recommends outside air for all installations, especially for those with
relatively air-tight homes or with vents that do not include vertical rise.

 Must not be drawn from an enclosed space (garage, unventilated crawl space).
 Must not be over 48” (1220mm) long
 Must be made with 1-¾” (45mm) diameter or larger metal or aluminum duct with a metal screen

attached to the end to keep out rodents (P.V.C. or other combustible materials may not be used).
We recommend the Travis Industries Outside Air Kit (part # 99200136).

 Must not terminate above or within 1' (305mm) of the chimney termination.
 Must have a rain cap or down-turned elbow to prevent water from entering.
 Must be located so that it will not become plugged by snow or other material.