Introduction

BE1-50/51M overcurrent relays are microprocessor based, non-directional phase or ground relays that

monitor the magnitude of a single-phase ac current to provide accurate instantaneous and time

overcurrent protection for 50 or 60 Hz power systems. Models are available with fifteen popular time

characteristics and a wide range of pickup settings.

Features

A wide range of pickup settings and front panel selectable time characteristics permit applications

involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.

Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51M overcurrent relays have the following standard features.

Independent time and instantaneous elements

A secure method to manually trip the breaker at the relay front panel

Direct reading front panel controls

Minimum pickup setting for safety during installation

Time characteristics extend to a pickup multiple of 40

Rugged draw-out construction with steel case

Gravity latching targets retain indication without power

Built-in accuracy eliminates internal adjustments

Minimum transient overreach

Field selectable characteristic curve selection

Field selectable instantaneous or integrating reset

Field selectable 50 or 60 Hz operation

Field selectable fixed instantaneous delay (0.0, 0.1, 0.2, or 0.3 second on 100 series relays and

0.0 or 0.1 second on 200 series relays.).

Individual models are available for 1 ampere and 5 amperes sensing input currents. BE1-50/51M

overcurrent relays (both horizontal and vertical mounts) must be removed from the case and installed on

a test bench for testing. Shorting contacts are provided for all current inputs when the relay chassis is

removed from the relay case. Figure 1-1 shows the front panel of the BE1-50/51M overcurrent relay, in a

C1, horizontal mount case. Figure 1-2 shows the front panel of the BE1-50/51M overcurrent relay, in a

C1, vertical mount case. Internally (circuit wise), all relay models are the same and use the same circuit

assemblies.

Advantages

BE1-50/51M overcurrent relays have many advantages over other overcurrent relays. The primary

advantages are:

Time characteristics are defined by equations and graphs

Field selectable time characteristics

Very low burden extends the linear range of the CTs

Self powered from the sensed current

Continuous automatic calibration