BE1-50/51M General Information

1-3

Model Numbers

Model number variations in the BE1-50/51M overcurrent relays are specified by a three digit extension to

the model number. Tables 1-1 and 1-2 provide model number, case style, switch SW3-3 selections, and

sensing current input ranges. Internal switches provide for selecting system operating frequencies of 50

or 60 Hz, instantaneous element delays, curve sets, and instantaneous or integrating reset

characteristics. The location and description of these switches is provided in Section 2. Integrating reset is

available in 100 series relays (e.g. - BE1-50/51M-100) when there is adequate input current to power the

relay. Integrating reset is available in 200 series relays (e.g. - BE1-50/51M-200) even when the input

current falls to zero. Two-hundred series relays also have additional characteristic curves available

through curve set selection.

Table 1-1. BE1-50/51M Overcurrent Relays, One Ampere CT Secondary, 50/60 Hz

Model Number

Case Style

SW3-3 Selects

Sensing Input Range (Amps)

TIME

INST

BE1-50/51M-100

C1 (Horizontal Mount)

0.2 Second Delay

0.1 - 3.18

0.2 - 19.8

BE1-50/51M-200

C1 (Horizontal Mount)

Curve Set

0.1 - 3.18

0.2 - 19.8

BE1-50/51M-108

C1 (Vertical Mount)

0.2 Second Delay

0.1 - 3.18

0.2 - 19.8

BE1-50/51M-208

C1 (Vertical Mount)

Curve Set

0.1 - 3.18

0.2 - 19.8


Table 1-2. BE1-50/51M Overcurrent Relays, Five Ampere CT Secondary, 50/60 Hz

Model Number

Case Style

SW3-3 Selects

Sensing Input Range (Amps)

TIME

INST

BE1-50/51M-104

C1 (Horizontal Mount)

0.2 Second Delay

0.5 - 15.9

1.0 - 99.0

BE1-50/51M-204

C1 (Horizontal Mount)

Curve Set

0.5 - 15.9

1.0 - 99.0

BE1-50/51M-109

C1 (Vertical Mount)

0.2 Second Delay

0.5 - 15.9

1.0 - 99.0

BE1-50/51M-209

C1 (Vertical Mount)

Curve Set

0.5 - 15.9

1.0 - 99.0



NOTE: 100 series relays (e.g. - BE1-50/51M-104) have the integrating reset function when there is

adequate input current to power the relay. 200 series relays (e.g. - BE1-50/51M-204) have the integrating

reset function even when the input current falls to zero.