Type tests, Environment, Agency recognition – Basler Electric BE1-50/51M User Manual

Page 20: Ul recognized/csa certified, Gost-r certification, Physical, Patent, Type tests -10, Environment -10, Agency recognition -10

Advertising
background image

1-10

BE1-50/51M General Information

9252000990 Rev R

Type Tests

Isolation ..................................... IEEE C37.90-2005

Transient Surge ......................... IEEE C37.90.1-2004

Radiated Interference ................ IEEE C37.90.2-2004

Electrostatic Discharge .............. IEEE C37.90.3-2006

Vibration ..................................... IEC 255-21-1

Shock and Bump ....................... IEC 255-21-2

Environment

Operating Temperature ............. –40°C to 70°C (–40°F to158°F)

Storage Temperature................. –50°C to 70°C (–58°F to 158°F).

Agency Recognition

UL Recognized per Standard 508, UL File No. E97033. CSA Certified per Standard CAN/CSA-C22.2 No.

14-M91, CSA File No. LR 23131.

UL Recognized/CSA Certified

Note: Output contacts are not UL Recognized/CSA Certified for voltages greater than 250 volts.

GOST-R certified per the relevant standards of Gosstandart of Russia.

GOST-R Certification

Physical

Weight ........................................ 5.2 lb (2.36 kg)

Patent

Patented in U.S., 1998, U.S. Patent No. 5751532.