Basler Electric BE1-50/51M User Manual

Page 25

Advertising
background image

9252000990 Rev R

BE1-50/51M Controls and Indicators

2-3

Table 2-1. BE1-50/51M Controls and Indicators (Refer to Figures 2-1 and 2-2)

Locator Control or Indicator

Function

A

INST MANUAL TRIP

Test Points

When shorted, the test points (jacks) provide a secure means to

manually trip the controlled breaker. Jacks accept a standard 0.08

inch diameter phone tip plug.

B

INST PICKUP

Selectors

Two switches (TENS and UNITS on five ampere models,

COARSE and FINE on one ampere models) to select pickup

current in amperes. Changing switch selectors while the relay is in

service may cause tripping.

C

Targets

Red target indicators latch when the trip circuit current is greater

than 0.2 amperes. One target each for TIME and INST.

D

TIME PICKUP

Selectors

Two switches (TENS and UNITS on five ampere models,

COARSE and FINE on one ampere models) to select pickup

current in amperes. Changing switch selectors while the relay is in

service may cause tripping.

E

CURVE Selector

Ten position selector switch to select one of nine inverse functions

or one fixed time function.

F

TIME DIAL Selectors

Two selector switches (UNITS and TENTHS) to select the desired

characteristic curve. A setting of 0.0 results in instantaneous

operation without any intentional delay. A setting of 9.9

corresponds to the typical time provided by an electromechanical

relay at its maximum dial setting.

G

TIME MANUAL TRIP

Test Points

When shorted, the test points provide a secure means to manually

trip the controlled breaker. Jacks accept a standard 0.08 inch

diameter phone tip plug.

H

ACTIVE/PICKUP LED This bicolor LED indicates the level of current sensed by the relay.

A green LED indicates that the relay is active but not picked up.

The LED changes to red when the sensed current exceeds the

time overcurrent pickup setting and back to green when the

sensed current decreases below 95% of the time overcurrent

pickup setting.
Note: A minimum of 0.5 A (5A units) or 0.1 A (1A units) is required

to light the LED. The LED may not turn green (active) before

turning red (picked up) at the 0.5 A pickup setting on 5A units or

0.1 A pickup setting on 1A units.

I

Target

RESET Button

Linkage extends through back of front cover to reset both gravity

latched target indicators.