Burden

Burden is non-linear. Figure 1-5 illustrates the device burden.

0.1 amperes ............................... 120 Ω

1 Ampere Unit

1.0 ampere ................................. 5 Ω

0.5 amperes ............................... 4.8 Ω

5 Ampere Unit

5.0 amperes ............................... 0.2 Ω

Figure 1-5. Burden Characteristics

Frequency Response

A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for

pickup.

Transient Response

<10% overreach with system time constants up to 40 ms.