Dropout, Curve characteristics, Figure 1-4. instantaneous characteristic curves – Basler Electric BE1-50/51M User Manual

Page 17

Advertising
background image

9252000990 Rev R

BE1-50/51M General Information

1-7

Dropout occurs at 95% of pickup value.

Dropout

BE1-50/51M instantaneous characteristic curves are similar to standard electromechanical instantaneous

units. However, the time to trip for ground applications is slightly longer than that for phase applications to

allow time to power up the relay. Longer trip time for ground applications is beneficial because it helps to

avoid nuisance trips.

Curve Characteristics

For phase applications, the maximum time to trip is 3.5 cycles at a pickup multiple of 1.0, and 1.5 cycles

at a pickup multiple of 3.0. The corresponding times for ground applications are 4.5 and 1.75 cycles.

Figure 1-4 shows the instantaneous characteristic curves for maximum time to trip.
On 100 series relays, additional delays of 0.1, 0.2, or 0.3 seconds may be added with internal switches

SW3-2 and SW3-3. These delays apply to both phase and ground applications. Closing switch SW3-2

provides an additional delay of 0.1 second. Closing switch SW3-3 provides an additional delay of 0.2

second. Closing both switches SW3-2 and SW3-3 provides an additional delay of 0.3 second. Section 2

illustrates the location of SW3.
On 200 series relays, an additional delay of 0.1 second may be added with internal switch SW3-2. This

delay applies to both phase and ground applications. Closing switch SW3-2 provides the additional delay

of 0.1 second.

Figure 1-4. Instantaneous Characteristic Curves

Advertising