Example 3: generator overload, Example 4: intertie, Example 3: generator overload -3 – Basler Electric BE1-32R User Manual

Page 13: Example 4: intertie -3, Figure 1-3. power relay start/stop control -3, Figure 1-4. power relay distribution protection -3

Advertising
background image

In the second configuration, the start signal is generated in the same manner as that of Figure 1-2. The

start signal setpoint may be set above the import power setting. The stop signal will require an

underpower relay on the generator output. This system is illustrated in Figure 1-3.

Example 3: Generator Overload
When excessive load has been connected to a generating system, the directional power relay can initiate

corrective action. Corrective action could be energizing an alarm to alert the station operator. For

automated systems, corrective action could be initiating the sequence to either shed non-critical load or to

start and parallel an in-house generator to assume the excess load.

Figure 1-3. Power Relay Start/Stop Control

Example 4: Intertie
Another typical use of the directional power relay, addresses excessive load and concerns distribution

protection (Figure 1-4). A high voltage bus supplies two transformers: T1 and T2. Both T1 and T2 can

supply all connected load. However, neither T1 nor T2 alone can supply the total load. A BE1-32O/U,

over/underpower directional relay can protect this distribution system by providing overload protection for

each transformer (overpower function) or by sensing power flow through the transformers (reverse power

function) in an undesired direction.

Figure 1-4. Power Relay Distribution Protection

9171100990 Rev R

BE1-32R, BE1-32O/U General Information

1-3

Advertising
This manual is related to the following products: