MAINTENANCE

BE1-32R and BE1-32O/U relays require no preventative maintenance other than testing performed

according to scheduled practices.

Repair
Repair of the draw-out assembly by replacement of individual circuit boards is not recommended. The

printed circuit boards are not intended to be field serviceable.
If a relay failure occurs in a critical application without sufficient redundancy, protection can be restored by

inserting a spare relay in the mounted and wired case of the relay requiring service. The draw-out

assembly requiring service can then be returned for service in the case from the spare relay. If a spare

case is not available, care should be used when packing the draw-out assembly for shipment. Use anti-

static packing material that prevents mechanical damage during transit.
Before returning a relay for repair, contact the Basler Electric Technical Services Department for a return

authorization number.

Maintenance Accessories
Test Plug
Test plugs (Basler P/N 10095) enable relay testing without removing the relay from the case. Test plugs

are simply substituted for the connection plugs. This provides access to the external stud connections as

well as the internal circuitry.
Test plugs consist of black and red phenolic moldings with 20 electrically separated contact fingers

connected to 10 coaxial binding posts. Fingers on the black side are connected to the inner binding posts

(black thumbnuts) and tap into the relay internal circuitry. Fingers on the red side of the test plug are

connected to the outer binding posts (red thumbnuts) and connect to the relay case terminals.
When testing circuits connected to the bottom set of case terminals, the test plug is inserted with the

numbers 1 through 10 facing up. Similarly, when using the test plug in the upper part of the relay, the test

plug is inserted with the numbers 11 through 20 facing up. Due to the construction of the test plug, it is

impossible to insert it with the wrong orientation.

STORAGE

This device contains long-life electrolytic capacitors. For devices that are not in service (spares in

storage), the life of these capacitors can be maximized by energizing the device for 30 minutes once per

year.

4-32

BE1-32R, BE1-32O/U Installation

9171100990 Rev T