Example 7: reactive power (vars) detection, Example 7: reactive power (vars) detection -6 – Basler Electric BE1-32R User Manual

Page 16

Advertising
background image

Example 7: Reactive Power (Vars) Detection
This example illustrates a directional power relay configured to distinguish between real and reactive

power. Real power (watts) is supplied to the synchronous generator by the prime mover, and reactive

power (vars) is supplied to the field by the exciter. When field excitation is significantly reduced and the

connected system can provide sufficient reactive power to maintain the generator terminal voltage,

reactive power flows into the machine and causes it to operate as an induction generator with essentially

the same kW output. This situation causes two major problems. First, the additional reactive loading of

the faulty generator must be redistributed to other synchronous generators on the system. Secondly, a

synchronous generator is not designed to operate as an induction generator. Excessive heating results in

the damper (amortisseur) windings, slot wedges, and in the surface iron of the rotor due to the slip

frequency current flow when a synchronous generator is operated as an induction generator.
BE1-32R and BE1-32O/U Directional Power Relays are designed to respond to true power (P) as defined

by the following equation and illustrated in Figure 1-10.

P = EI (cos θ)

where: P = real power (watts)

I = effective current

E = effective EMF or system voltage

θ

= the power factor angle

However, reactive power (Q) is defined by the equation:

Q = EI (sin θ)

Using the trigonometric identity sine θ = cos(θ – 90 )

then: Q = EI (cos(θ – 90 ))

If the phase of the sensed voltage is shifted +90°, the true power relay can be used to monitor reactive

power. In practice, this can be accomplished by applying the appropriate line-to-line voltage to a true

power measuring relay designed for line-to-neutral sensing. Figure 1-11 illustrates how a single-phase

BE1-32R or BE1-32O/U can be connected to measure either real power (watts) or reactive power (vars)

flow in a three-phase system. Note the difference of phase relationship between the alternate connections

in Figure 1-11.

Figure 1-10. True

Power Response

1-6

BE1-32R, BE1-32O/U General Information

9171100990 Rev T

Advertising
This manual is related to the following products: