Figure 5-4. type d sensing test connections -7, Figure 5-4 – Basler Electric BE1-32R User Manual

Page 79

Advertising
background image

NOTES

1. Type D sensing is calibrated in three-phase watts using single-phase sensing inputs. Using the test connections

shown, the relay may be calibrated in true three-phase power using one-third of the pickup current corresponding

to the desired overpower or underpower pickup in watts. Adjust the relay test set to produce this current value

from the following equation.

𝑊 = 3 × 𝑉

𝐴

× 𝐼

W is the desired pickup in watts.

V is the applied voltage.

I is the applied current.
With a wattmeter, W is determined by the following equation.

𝑊 = 2 × 𝑊𝑎𝑡𝑡𝑚𝑒𝑡𝑒𝑟 𝑅𝑒𝑎𝑑𝑖𝑛𝑔

2. Terminals 1 and 10 are the overpower trip output device connections for both BE1-32R and BE1-32O/U.

Terminals 2 and 10 are the underpower output connections for the BE1-32O/U.

3. Terminals 17 through 20 are auxiliary output contacts. Determine the auxiliary output contact configuration by

referring to the relay style number.

Figure 5-4. Type D Sensing Test Connections

9171100990 Rev T

BE1-32R, BE1-32O/U Testing

5-7