Introduction, Test procedures, Connections – Basler Electric BE1-32R User Manual

Page 73: Overpower pickup and dropout (unity power factor), Underpower pickup and dropout (unity power factor), Section 5 • testing -1, Introduction -1, Test procedures -1, Connections -1

Advertising
background image

SECTION 5 • TESTING

INTRODUCTION

The following procedures verify proper relay operation and calibration.
Results obtained from these procedures may not fall within specified tolerances. When evaluating results,

consider three prominent factors:

Test equipment accuracy

Testing method (e.g., timing start signal)

External test set components tolerance level

TEST PROCEDURES

Connections
Relay test connections depend upon the relay sensing type. Connect the relay using the appropriate

illustration as a reference.
Type A sensing:

Figure 5-1

Type B, V sensing: Figure 5-2

Type C sensing:

Figure 5-3

Type D sensing:

Figure 5-4

Type E sensing:

Figure 5-5

Overpower Pickup and Dropout (Unity Power Factor)
1. Make the following relay front panel setting adjustments. Note that relays with inverse or

instantaneous timing options will not have an Overpower Time Delay Multiplier Switch.

Range Select Switch: LOW

Overpower Tap Selector: B

Overpower Time Delay Control: 00 (instantaneous)

Overpower Time Delay Multiplier Switch: x0.1

Underpower Pickup Selector: FULLY CCW

2. Apply operating power to the relay at case terminals 3 and 4.
3. Apply nominal sensing input voltage to the appropriate case terminals. A single voltage source may

be connected to paralleled relay sensing voltage inputs to simulate a three-phase source.

4. Apply a current source to the relay current sensing inputs and increase the current level until the

Overpower Pickup Indicator just lights.

The Overpower output contacts, auxiliary output contacts, and target indicators should operate.

Verify that the wattmeter indicates a power reading that is within 2% of the Overpower Tap Selector

setting. The pickup setting for tap B, low range is listed on the front panel Tap Selection Chart.

5. Slowly reduce the applied current until the Overpower Pickup Indicator just turns off.

Verify that the wattmeter indicates a power reading that is within 98% of the pickup value established

in step 4.
Reset the target indicators.

6. Repeat steps 4 and 5 for Overpower Tap Selector settings of E and K.

Underpower Pickup and Dropout (Unity Power Factor)
1. Make the following relay front panel setting adjustments. Note that relays with inverse or

instantaneous timing options will not have an Overpower Time Delay Multiplier Switch.
Underpower Time Delay Multiplier Switch: LOW

Underpower Pickup Selector: FULLY CW

Underpower Time Delay Control: 00 (instantaneous)

Overpower, Underpower Time Delay Multiplier Switch: x0.1

Overpower Tap Selector: B

2. Apply operating power to the relay at case terminals 3 and 4.
9171100990 Rev T

BE1-32R, BE1-32O/U Testing

5-1

Advertising
This manual is related to the following products: