Relays with type E sensing (two elements) monitor two phase-to-phase voltages (the third phase is used

as a reference) and two phases of current to determine directional power flow. This is sometimes referred

to as the two-wattmeter method for power flow measurement. Figure 3-2 shows the phasor representation

for ABC rotation. Figure 3-3 shows the phasor representation for ACB rotation.

Figure 3-2. Type E Sensing with ABC Rotation

Figure 3-3. Type E Sensing with ACB Rotation


Type B and V Sensing
Relays with type B sensing (60 hertz) and type V sensing (50 hertz) monitor one phase-to-phase voltage

and one phase of current to determine directional power flow. An internal 30-degree phase delay network

(frequency dependent) aligns the voltage signal with the current signal. Figure 3-4 shows the phasor

representation for monitoring A-phase to B-phase voltage and A-phase current with ABC rotation. Figure

3-5 shows the phasor representation for monitoring A-phase to C-phase voltage with ACB rotation.

Figure 3-4. Type B or V Sensing with ABC Rotation

3-2