Timing—continued, Accuracy, Power range (pickup) – Basler Electric BE1-32R User Manual

Page 23: Type tests, Dielectric strength, Surge withstand capability (swc), Timing—continued -13, Power range (pickup) -13, Type tests -13, Table 1-4. power pickup ranges -13

Advertising
background image

Timing—continued
Accuracy
Instantaneous:

<80 ms (60 Hz) or <100 ms, (50 Hz) up to a real power

magnitude of 2 times the setting

Definite:

±

5 percent or 50 ms, whichever is greater

Inverse:

+

5 percent or 50 ms, whichever is greater

NOTE: Operating time is repeatable within 2% or 50 ms

(whichever is greater) for any combination of time dial and power

settings within the specified operating temperature range.

Power Range (Pickup)
The power pickup range is adjustable over the ranges listed in Table 1-4.

Table 1-4. Power Pickup Ranges

Sensing

Input Type

Nom.

Volts Range

Switch Position (in watts)

A

B

C

D

E

F

G

H

J

K

A, B or V

1-phase

120

1

Hi 2.0

4.0

6.0

8.0

10.0 12.0 14.0 16.0 18.0

20.0

Lo 0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

2

Hi 20

40

60

80

100

120

140

160

180

200

Lo

5

10

15

20

25

30

35

40

45

50

3

Hi 100 200

300

400

500

600

700

800

900

1000

Lo 25

50

75

100

125

150

175

200

225

250

C, D, or E

3-phase

120

1

Hi 6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0 54.0

60.0

Lo 1.5

3.0

4.5

6.0

7.5

9.0

10.5 12.0 13.5

15.0

2

Hi 60

120

180

240

300

360

420

480

540

600

Lo 15

30

45

60

75

90

105

120

135

150

3

Hi 300 600

900 1200 1500 1800 2100 2400 2700 3000

Lo 75

150

225

300

375

450

525

600

675

750

A, B, or V

1-phase

208

or

240

4, 7 Hi 4.0

8.0

12.0 16.0 20.0 24.0 28.0 32.0 36.0

40.0

Lo 1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0

5, 8 Hi 40

80

120. 160

200

240

280

320

360

400

Lo 10

20

30

40

50

60

70

80

90

100

6, 9 Hi 200 400

600

800 1000 1200 1400 1600 1800 2000

Lo 50

100

150

200

250

300

350

400

450

500

C, D, or E

3-phase

208

or

240

4, 7 Hi 12.0 24.0 36.0 48.0 60.0 72.0 84.0 96.0 108.0 120.0

Lo 3.0

6.0

9.0

12.0 15.0 18.0 21.0 24.0 27.0

30.0

5, 8 Hi 120 240

360

480

600

720

840

960 1080 1200

Lo 30

60

90

120

150

180

210

240

270

300

6, 9 Hi 600 1200 1800 2400 3000 3600 4200 4800 5400 6000

Lo 150 300

450

600

750

900 1050 1200 1350 1500

Type Tests
Dielectric Strength
Tested in accordance with IEC 60255-5 and IEEE C37.90. Withstands the following tests.
All circuits to ground:

2,121 Vdc

Input to output circuits:

1,500 Vac or 2121 Vdc

Surge Withstand Capability (SWC)
Qualified to IEEE C37.90.1-1989, Standard Surge Withstand Capability (SWC) Tests for Protective

Relays and Relay Systems

9171100990 Rev R

BE1-32R, BE1-32O/U General Information