Figure 1-9. underpower tripping -5, Ee figure 1-7), Figure 1-7 – Basler Electric BE1-32R User Manual

Page 15

Advertising
background image

Figure 1-7. Power Factor, First and Second Quadrants

When breaker N opens, operation transfers to the third or fourth quadrants (see Figure 1-8). If transformer

exciting current predominates, operation falls in the third quadrant. If cable charging current pre-

dominates, operation falls in the fourth quadrant. In either case, the transformer losses must be supplied.

In Figure 1-8, a real current component of four milliamperes is shown and represents core losses of the

transformer (about 0.1% of rated).

Figure 1-8. Power Factor, Third and Fourth Quadrants

When breaker N opens, real power reverses from normal and flows toward the utility. This power may be

flowing to the tapped load. At this time, the relay operates and causes the 52 breaker to open.
Figure 1-9A shows an underpower tripping application based on the BE1-32O/U, model A1F with an

overpower setting of 0.5 watts and an underpower setting of 50%. The control circuit for this application is

shown in Figure 1-9B. Figure 1-10 shows the operating characteristic in the first and second quadrant.

The relay Under contact closes to trip the breaker when the real power flow from the utility drops below

0.25 watts. Because this contact is pre-closed at the instant of breaker closing, the trip circuit must be

disabled by a timing relay (62) until after the breaker has closed.

Figure 1-9. Underpower Tripping

9171100990 Rev R

BE1-32R, BE1-32O/U General Information

1-5