Current and Voltage Settings

Voltage Alarm Pickup ............................. 10 to 80% in 10% increments
Voltage Pickup ........................................ 50 to 400 V in 50 V increments
Current Pickup ........................................ 0.25 to 2.5 A in 0.25 A increments

Table 1-2 describes input impedance while the SCRs are triggered (low impedance) and while the SCRs
are not triggered (high impedance).

Table 1-2. Input Impedance While Triggered and Not Triggered

Impedance State

Input Impedance in Ohms

60 Hz Nominal

50 Hz Nominal

Low Impedance (SCRs Triggered, Current Circuit Active)

0.05

0.05

High Impedance (SCRs Not Triggered, Voltage Circuit Active)

4000 - j3300

5100

∠ –40°

4500 - j3100

5500

∠ –35°

Frequency

Nominal 50 or 60 Hz,

± 5 Hz

Pickup Accuracy

±5% of the setting over the operating ranges for both current and voltage. Pickup accuracy over the ±5 Hz
nominal frequency variation is within

±8% of the nominal frequency value.

Output Contacts

Output contacts are rated as follows.

Resistive

120/240 Vac ............................................ Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, break

7 Aac

125/250 Vdc ............................................ Make and carry 30 Adc for 0.2 s, carry 7 Adc continuously, break

0.3 Adc

Inductive

120 Vac, 240 Vac, 125 Vdc, 250 Vdc ..... Break 0.1 A (L/R = 0.04)

Current Rating

Continuous .............................................. 10 A rms
1 second, symmetrical ............................ 160 A rms
5 cycles, symmetrical ............................. 480 A rms
2 cycles, fully offset ................................ 215 A

Voltage Rating

The nature of the BE1-87B relay’s application is that voltage is not applied continuously. For calibration
and test purposes, it may be of value to apply input voltage for a longer duration than the few milliseconds
that would typify an internal or external power system fault. For test and calibration purposes, the BE1-
87B has been designed to withstand 300 Vac for a maximum duration of 60 minutes.

Targets

LED indication (Trip LED) is latched with an internal, mechanical latching relay. Reset is accomplished by
pressing the Reset button on the front panel.

Isolation

In accordance with IEC 255-5 and IEEE C37.90, one-minute dielectric (high potential) tests were
performed as follows.

All circuits to ground ............................... 2000 Vac or 2828 Vdc
Each circuit to all other circuits ............... 2000 Vac or 2828 Vdc.

9282300990 Rev P