Surge withstand capability (swc), Impulse test, Radio frequency interference – Basler Electric BE1-87B User Manual

Page 16: Electrostatic discharge (esd), Ul recognition, Gost-r certification, Environment, Shock, Vibration, Weight

Advertising
background image

Surge Withstand Capability (SWC)

Oscillatory and Fast Transient ................ Qualified to IEEE C37.90.1-1989

Impulse Test

Qualified to IEC 255-5.

Radio Frequency Interference

Maintains proper operation when tested for interference in accordance with IEEE C37.90.2 1995.

Electrostatic Discharge (ESD)

In accordance with IEEE C37.90.3, contact discharges of 8 kilovolts and air discharges of 15 kilovolts
were applied with no misoperation occurring.

UL Recognition

Recognized per Standard 508, UL File Number E97033.

Note that output contacts are not UL recognized for voltages greater than 250 V.

GOST-R Certification

GOST-R certified per the relevant standards of Gosstandart of Russia.

Environment

Temperature

Operating Range ....................................

−40°C to 70°C (−40°F to 158°F)

Storage Range ........................................

−40°C to 85°C (−40°F to 185°F)

Humidity

Qualified to IEC 68-2-38, First Edition 1974

Shock

Qualified to IEC 255-21-2, Class 1.

Vibration

Qualified to IEC 255-21-1, Class 1.

Weight

1-phase Relay ......................................... 14.3 lb (6.5 kg) maximum
3-phase Relay ......................................... 19.2 lb (8.8 kg) maximum

Case Size

1-phase Relay ......................................... S1
3-phase Relay ......................................... M1 or 19” Rack-Mount

Case dimensions are provided in Section 4, Installation.

1-4

BE1-87B Application

9282300990 Rev P

Advertising