INTRODUCTION

This instruction manual provides information about the operation and installation of the BE1-87B Bus
Differential Relay. To accomplish this, the following information is provided:

General Information and Specifications

Controls and Indicators

Functional Description

Installation

Testing

WARNING!

To avoid personal injury or equipment damage, only qualified personnel should
perform the procedures in this manual.

The paddle plugs should be removed prior to performing a current circuit
insulation test. The design of the voltage-sensing circuit creates a low
resistance path to ground when the paddle plugs are installed, which results in
incorrect test results.

NOTE

Be sure that the BE1-87B is hard-wired to earth ground with no smaller than
12 AWG copper wire attached to the ground terminal on the rear of the unit
case. When the BE1-87B is configured in a system with other devices, it is
recommended to use a separate lead to the ground bus from each unit.

9282300990 Rev P