BECKHOFF CX1100-000x User Manual

Page 39

Advertising
background image

Product overview

Embedded PC

37

the K-Bus reset, the error code and error argument may be read from the locations "K-Bus error code" and "K-Bus
error argument" in the CB K-Bus. If there is no error after reset, the K-Bus is ready for operation again.

Free Run:
not implemented. Reserved for future use..

IP-Link error code K-Bus error argument

If the K-Bus operation fails (bad terminal, missing end-terminal, severe EMC interference), an error flag is raised in
the GCB and after a K-Bus reset, these two bytes contain the error code and error argument of the occurred fault - if
it still persists.

IP-Link base ptr Inputs / K-Bus base ptr Outputs

These two byte values contain the starting offset for the K-Bus input and output process image area. In most cases
the default offsets should be left unchanged. When changing one of these offsets, a "Remap" or "Reset node" in the
GCB service is needed. Also care must be taken not to overlap with the IP-Link process image area, because in the
CB IP-Link the offset pointers for these areas may also be changed. The Beckhoff automation software TwinCAT
makes use of this base ptr feature and compacts the I/O images in the best way possible.

IP-Link cycle count

This two-byte counter is incremented with each I/O-cycle.

IP-Link cycle time

This is the time elapsed between the initiation and termination of an I/O process image update (K-Bus + IP-Link ).
The time is recorded in units of microseconds and starts with writing a new cycle request to the field "PD cycle
request" and it stops with the termination response in the field "PD cycle ready", in case of CX1100-0002. In case of
CX1100-0003, this time reflects only the K-Bus portion of the total I/O time.

IP-Link bus status

This byte value can take only two states:

1.

Byte = 0 →

K-bus is ok

2.

Byte ≠ 0 → K-bus fault

This information is also reflected in the "Processdata error" field (bit0) of the GCB.

Retry counter

This is a retry counter which is incremented each time the microcontroller needs to redo a cycle because of a
communication error. This counter can be used for judgment of the K-Bus signal quality.