Error handling and diagnostics

Embedded PC

51

ip_bus_err_code

with

ErrorCode

ip_bus_err_arg

with

ErrorArg

ip_bus_state

with

BusState

ip_bus_request

with

Request[0]

If all signals are linked the programmer can load configuration and PLC program onto the system.

Firmware > B7

With a new firmware release B7 it is easier to access the diagnosis values. The solution described above clears the
error code if the reason for the error is no longer present. With the firmware > B7 its possible to get the error codes
directly in the case of the error. To access the error codes the Bit 4 in GCB must be set to 1. So for diagnosis its a
good idea to set the bit in the initialization of error routine or PLC program. The bit must be linked to the bit 4 in GCB: