BECKHOFF CX1100-000x User Manual

Page 51

Advertising
background image

Error handling and diagnostics

Embedded PC

49

....

IF k_bus_state = 1

THEN

(* an error occured on K-Bus*)

k_bus_request := TRUE;

(* request vaules for ErrCode and ErrArg *)

CASE k_bus_err_code OF

0 : return;

(* should not happen, though an error occured *)

1 : CASE k_bus_arg OF

0 : report error;

(* EEPROM checksum error *)

1 : report error;

(* overflow in code buffer *)

2 : report error;

(* unknown datatype *)

END_CASE;

2 : CASE k_bus_arg OF

0 : report error;

(* programmed configuration, wrong table entry *)

ELSE report error;

(* wrong table entry *)

END_CASE;

3 : report error

(* K-Bus command error *)

4 : CASE k_bus_arg OF

0 : report error;

(* break after power supply *)

ELSE report error;

(* break after terminal 'k_bus_arg' *)

END_CASE;

5 : report error

(* K-Bus-error during register-communication with

terminal 'k_bus_arg' *)

9 : CASE k_bus_arg OF

0 : report error;

(* checksum error in program flash *)

ELSE report error;

(* terminal 'k_bus_arg' does not exist in boot

configuration *)

END_CASE;

14 : report error

(* 'k_bus_arg'-th terminal has wrong format *)

15 : report error

(* wrong number of bus terminals *)

16 : report error

(* length of K-Bus data is invalid *)

END_CASE

k_bus_request := TRUE;

(* reset bus, if reason for error is removed, bus

starts again *)

....

To make the control work, the register and the program must be linked in System Manager. If the PLC program is
attached in System Manager the following signals are available: