Error handling and diagnostics

56

Embedded PC

0

Checksum error in Flash
program

Revert to the manufacturer’s setting

9 pulses

n (n>0)

Bus Terminal n is not
consistent with the
configuration that existed
when the boot project was
created

Revert to the manufacturer's setting which will
clear the boot project.

14 pulses

n

nth Bus Terminal has the
wrong format

Start the power supply again, and if the error
occurs again then exchange the Bus
Terminal.

15 pulses

n

Number of Bus Terminals is
no longer correct

Start the power supply up again.

16 pulses

n

Length of the K-Bus data is
no longer correct

Start the power supply up again.

Error code argument
The number of pulses indicates the position of the last Bus Terminal before the fault. Passive Bus Terminals, such as
a power feed terminal, are not included in the count.

In the case of some errors, rectification does not cause the power supply to leave the blink sequence. The power
supply can only be restarted by switching its supply voltage off and on again.

Note:
The power source to the power supply unit which is necessary to supply power to the CX-system, must not be
interrupted during operation. Switching off the supply voltage to the power supply unit refers here to the power supply
on the power contacts.

LEDs for IP-Link-diagnosis

LEDs for IP-Link-Bus-Diagnosis

After a long flash (app.. 2 sec.) an IP-Link-Bus error has occurred. The following tables describe the error codes and
help to find the reason for the error. IP-Link errors most often turn out to be a result of inappropriate use of the optical
fiber.

I/O Err

Description

Remedy

off

No data exchange

Module in synchronous mode or - activate
Profibus cyclic data

1

0

EEPROM checksum error

Set manufacturer’s setting with the KS2000
software

2

Reserved

-

3

Break location has been recognized

Interruption before the master's receiver

3

n

Break location has been recognized

n-th module before the master's receiver

3

n

m

Break location has been recognized

(n*10)+m-th module before the master's
receiver

4

n

Too many faulty telegrams have
been detected (more than 25%)

The optical fiber wiring in front of the nth
extension module should be checked