OPERATION (cont.)

Self-Diagnostic Codes

Self-diagnostic codes are displayed on the control board under the following

conditions.

Contact your MovinCool reseller or a qualified technician if problem persists.

LCD Display Codes

Condition

When the drain tank switch shuts off the unit, LCD

displays “TANK FL” and “TANK FULL” LED flashes.

Once emptying the drain tank procedure is

completed and ON/OFF has been pushed, unit

returns to normal operation.

When the condensate pump stops pumping water

due to any kink and/or blockage in the drain line or

due to improper routing of the drain line, the

compressor shuts off, and the LCD displays “AS”.

Once the condition is fixed and unit has been

RESET, the unit returns to normal operation.

To RESET: Press FAN HI/LO and COOL ON/OFF

buttons simultaneously for 5 seconds.

When high pressure switch is activated for the first

2 times in 24 hours, display shows “HP” but goes

away as the high pressure switch resets. If the high

pressure switch is activated 3 times in 24 hours, unit

displays blinking “HP” and a buzzer turns on (see

page 34). Unit returns to normal operation after

problem is fixed and controller is RESET.

To RESET: Press FAN HI/LO and COOL ON/OFF

buttons simultaneously for 5 seconds.

When room thermistor becomes open or shorted,

display shows “OPEN RT” or “SHRT RT” and cool

mode operation is off. Display and cool mode

operation are returned to normal operation after

room thermistor is fixed.

When freeze thermistor becomes open or shorted,

display shows “OPEN FT” or “SHRT FT” and cool

mode operation is off. Display and cool mode

operation are returned to normal operation after

freeze thermistor is fixed.

When the unit detects a signal from the fire alarm

system, the display shows "ALRM" and a buzzer

turns on. Check the fire alarm system and confirm

that there is no signal input to the unit. The unit

returns to the normal operation after the problem is

fixed and the controller is RESET.

To RESET: Press FAN HI/LO and COOL ON/OFF

buttons simultaneously for 5 seconds.