Technical specifications (cont.) – MovinCool Office Pro W20 User Manual

Page 36

Advertising
background image

36

TECHNICAL SPECIFICATIONS (cont.)

• Specifications are subject to change without notice.
Note:
*1: If the entering water temperature is below 68 °F (20 °C) or above 86 °F (30 °C),

adjustment of the unit's water regulating valve setting is required.

*2: Measured at 3 feet (1.0 m) from surface of the unit.

ITEM

SPECIFICATIONS

Operating Condition Range

Inlet Air

Temperature

Max.

95 °F (35 °C), 60 %RH

Min.

65 °F (18 °C), 50 %RH

Entering Water
Temperature

*1

Max.

90 °F (32 °C)

Min.

40 °F (4.4 °C)

Water Pressure

150 psi (1,034 kPa) or less

Recommended Water

Flow Rate

5 gal/min (18 L/min)

Maximum Duct Length

Cold Duct

25 ft (7.6 m)

Sound Level

*2

High

62 dB (A)

Low

60 dB (A)