Top view side view, Pressure independent velocity sensor, Warning – Orion System OE217-00 User Manual

Page 31

Advertising
background image

Notes:

C

O

N

T

R

O

L

S

FILENAME

DATE:

B. THRALL

DESCRIPTION:

PAGE

DRAWN BY:

Pressure Independent Velocity Sensor

1

JOB NAME

2.)All Wiring To Be In Accordance With Local And

National Electrical Codes And Specifications.

10/20/01

PITRAN1.5.CDR

OE274

Top View

Side View

OUT

IN

GND

UP

(-)LO

0.35"

0.55"

1.00"

2.20"

0.15" DIA.

0.15"

2.94"

2.50"

0.125" (1/8" Tubing Conn.)

0.200" (3/16" Tubing Conn.)

1.95"

0.60"

12.0" APPROX.

Full Scale Output

(Positive Pressure)

Null Offset
Span*

Minimum

Typical

Maximum

Hystereisis And Repeatability

Temperature Error

Null +10 To 40 C

°

°

Stability (1 Year)

Supply Voltage (Vs)

Pressure Overload

Burst Pressure

Positive Pressure (Hi Side)

Negative Pressure (Lo Side)

Positive Pressure (Hi Side)

Negative Pressure (Lo Side)

Non-Linearity

Span +10 To 40 C

°

°

Common Mode Pressure

0-1.5“ H O Pressure Range - 5 VDC Operation

2

3.92 VDC

0.17 VDC

0.2-0.3 VDC

0.33 VDC

3.59 VDC

3.91 VDC

±0.05 % Span

4.75 VDC

5.0 VDC

8.0 VDC

15 PSI

5“ H O

2

10“ H O

2

3“ H O

2

5“ H O

2

4.08 VDC

3.95-4.05 VDC

3.65-3.85 VDC
±0.3 % Span

±0.5 % Span

±0.03 % Span

±1.0 % Span

±0.5 % Span

±1.0 % Span

±1.5 % Span

±1.5 % Span

*Span Is The Algebraic Difference Between End Points (Null Offset And Full Scale Output)

The plastic housing on the sensor is electrically

conductive. Avoid contact with any electrical components.

It is acceptable to mount the sensor on grounded sheet

metal such as ductwork, electrical panels, etc.

Use extreme care when mounting the sensor to avoid

damage to the plastic housing. Do not overtighten the

mounting screws! Do not use mounting screws which are

too large for the holes!

Warning!

Warning!

1.)

The Velocity Pressure Sensor Should Be

Mounted In A Vertical Position As Shown With

Arrow Pointing Up. ( Tubing Connections Pointing

Down). If This Mounting Position Is Not Possible In

Your Application, It May Be Mounted In A Horizontal

Position. When Mounted In A Horizontal Position

Accuracy Will Be Affected By Approximately 2% Full

Scale Null Shift Due To Diaphragm Gravity Effect

Error.

Caution:

OE274 - Velocity Pressure

For P. I. VAV/Zone Control

Sensor

1.29"

OUT

(Black)

GND

(Green)

IN

(Red)

±1 % Span

OE274

P.I. Sensor

Advertising
This manual is related to the following products: