Setra, 2( ² %xloglqj 3uhvvxuh 6hqvru, Description – Orion System OE217-00 User Manual

Page 32

Advertising
background image

Form: ORION-OE258-6-BuildingPressureSensor-1B.doc

Page

1 of 1

Description

The OE258 Building Static Pressure Sen-
sor is used to sense building pressure in
applications where monitoring of the
building static pressure is required to in-
sure the building maintains the proper air
pressurization.

The OE258 Building Pressure Sensor
case is molded from fire retardant glass
filled polyester. The sensor utilizes a ten-
sioned stainless steel diaphragm and in-
sulated stainless steel electrode. This
arrangement allows up to 10 PSI over-
pressure without damage to the unit. The
sensor provides a 0.0 to 5.0 VDC output
in response to a –0.25 to +0.25 inch WC
pressure differential. Accuracy is

±

1% of

full scale of the sensor.

For easy wiring the OE258 Building Static
Pressure Sensor has (3) 6-32 screw ter-
minal wiring connectors. The sensor has
(2) ¼” barbed fittings provided for the
connection of tubing to the high and low
pressure ports.

The OE258 Static Pressure Sensor is
designed to be mounted to a flat surface
by means of the (2) 0.156 diameter holes
provided in the sensor casing. For accu-
rate readings the sensor must be
mounted in a vertical position.

Technical Data

OE258 - Building Static

Pressure Sensor

Operating Pressure
Range

-0.25” WC to +0.25” WC

Pressure Differential

Power Input
Signal Output

9-30 VDC

0 to 5 VDC

Operating Temp

0

°

F to 150

°

F

Hysteresis

±

0.1% of full scale

Circuit

3 Wire

Non-repeatability

±

0.05% of full scale

Accuracy

±

1% of full scale

Weight

3 ounces

Three Year Warranty

WattMaster reserves the right to change specifications without notice

HIGH

MODEL 265

LOW

-

+

+

+

1.89

0.95

3.16

2.74

setra

0.95

1.64

0.156 DIA. HOLE

TYP. 2 PL.

2( ² %XLOGLQJ 3UHVVXUH 6HQVRU

Advertising
This manual is related to the following products: