Description

The OE256-02 Duct Mounted CO

2

Sensor

is used in conjunction with the VCM-X Con-
troller (OE332-23-VCMX) to monitor and
control CO

2

levels in the building environ-

ment. It can be configured via its address
switch to be either a Supply Air CO

2

Sen-

sor or Return Air CO

2

Sensor as required.


Some typical applications are:

Demand Control Ventilation

Controlling ventilation in a building
where the occupancy varies fre-
quently

Controlling ventilation based on CO

2

levels to ensure excess outdoor air is
not causing energy waste

To ensure good air distribution
throughout building zones

The OE256-02 is used for monitoring duct
CO

2

levels and is designed for permanent

duct mounting in the Supply or Return Air
duct. It utilizes an aspiration box to accu-
rately capture CO

2

levels in the Supply or

Return Air duct. It connects to the VCM-X
by using a modular prefabricated cable with
RJ-45 connectors. It can be daisy chained
with the Orion Modular Room Temperature
Sensor or Digital Room Temperature Sen-
sor for applications requiring both a room
CO

2

sensor and room temperature sensor.

The OE256-02 CO

2

Sensor uses non-

dispersive infrared (NDIR) technology and
has a measurement range of 0-2000 ppm.

Mounting

The OE256-02 CO

2

Sensor is housed in an

aspiration box. The sensor has an integral
mounting sub-base mounting plate with
modular phone jacks for connecting it to
the VCM-X and another Digital or Modular
Room Temperature Sensor. A conduit
clamp is provided to help seal the opening where the sensor cabling penetrates the aspiration box housing. The sensor and
aspiration box assembly is mounted to the ductwork by first cutting a 1

1

/

4

” diameter hole in the duct wall for insertion of the as-

piration tube. The aspiration tube is then inserted into the hole. The aspiration box sensor assembly is then secured to the
ductwork by inserting (4) supplied sheet metal screws through (4) mounting holes in the aspiration box base and securing the
assembly by screwing it to the ductwork using a manual or powered screw driver to tighten the screws.










Technical Data

OE256-02 Duct Mounted CO

2

Sensor

Input Power

12-34 VDC

Power Consumption

30 mW Maximum Average

1.25 W Peak Power

Operating Temperature

14

° to 122° F Operating Humidity

5-95% RH Non-Condensing

Sample Method

Flow-Through

50-100 ml/min

Measurement Range

0 to 2000 ppm

Sensitivity

<

±20 ppm Resolution

±1 ppm

Accuracy

±50 ppm @ 1000 ppm or 2%

measured value

Communications I

2

C

One Year Warranty

WattMaster reserves the right to change specifications without notice