Super Systems 7EK 31082 User Manual

Page 13

Advertising
background image

8

GB

SEr1 = Serial interface protocol

OFF

= No serial interface

Ero

= Polling/selecting ERO

ñbUS

= Modbus

jbUS

= Jbus

SEr2 = Serial link device address
Not available when SEr1 = OFF
From 1 to 95 for ERO protocol
From 1 to 255 for all the other protocols
NOTE: the electrical characteristic of the RS 485 serial
interface will allow the connection of 31 devices maximum.

SEr3 = Baude rate for serial link
Not available when SEr1 = OFF
From 600 to 19200 baud.
NOTE: 19200 baud is shown on display as 19.2.

SEr4 = Byte format for serial link
Not available when SEr1 = OFF
7E

= 7 bits + even parity (For ERO protocol only)

7O

= 7 bits + odd parity (For ERO protocol only)

8E

= 8 bits + even parity

8O

= 8 bits + odd parity

8

= 8 bits without parity

P1 - Input type and standard range
0

= TC type

L

range

0 /

+400.0 °C

1

= TC type

L

range

0 /

+900 °C

2

= TC type

J

range

-100.0 /

+400.0 °C

3

= TC type

J

range

-100 /

+1000 °C

4

= TC type

K

range

-100.0 /

+400.0 °C

5

= TC type

K

range

-100 /

+1370 °C

6

= TC type

T

range

-199.9 /

+400.0 °C

7

= TC type

N

range

-100 /

+1400 °C

8

= TC type

R

range

0 /

+1760 °C

9

= TC type

S

range

0 /

+1760 °C

10 = TC type

B

range

0 /

+1820 °C

11 = RTD type

Pt 100

range

-199.9 /

+400.0 °C

12 = RTD type

Pt 100

range

-200 /

+800 °C

13 = mV

Linear

range

0 /

60 mV

14 = mV

Linear

range

12 /

60 mV

15 = mA

Linear

range

0 /

20 mA

16 = mA

Linear

range

4 /

20 mA

17 = V

Linear

range

0 /

5 V

When it is desired to exit from configuration modify mode
proceed as follows:
a) Push "FUNC" or "MAN" push-button more times until

the "C.End" parameter is displayed.

b) Pushing ”

s” or “t” push-button select the "YES"

indication.

c) Push “FUNC” push-button. The instrument ends the

configuration modify mode, preforms an automatic
reset and restarts in the run time mode.

Pushbutton function during configuration mode
FUNC =

This will memorize the new value of the
selected parameter and go to the next
parameter (increasing order).

MAN =

This will scroll back the parameters without
memorization of the new value.

s =

This will increase the value of the selected
parameter

t =

This will decrease the value of the selected
parameter.

CONFIGURATION PARAMETERS
Notes:
1) In the following pages we will describe all the

parameters of the instrument but the instrument will
show only the parameters related with the specific
hardware and in accordance with the specific
instrument configuration (i.e. setting OUT 3 (P7) =
nonE, (not used), all the parameters related with this
output will not be displayed).

2) During configuration mode, the lower display shows

the mnemonic code of the selected parameter while
the upper display shows the value or the status
assigned to the selected parameter.

dF.Cn = Load default configuration data

OFF

= No default data loading

tb.1

= Load table 1 default data loading (european)

tb.2

= Load table 2 default data loading (american)

For more datails see appendix A.

XKSser1-A0.p65

10/19/01, 1:37 PM

8