15

GB

P55 =

Security code for configuration parameters

0

No protection (it is always possible to modify all
configuration parameters);

1

Always protected (it is not possible to modify any
configuration parameter);

from 2 to 9999 security code for configuration parameter

protection.

Notes:
1) If a value from 2 to 9999 has been assigned as security

code it cannot be displayed anymore, when returning
on this parameter the display will show "On".

2) If the security code is forgotten a master key code is

available, by this code it is ever possible to enter in
modify configuration mode (S.CnF = 1 or from 2 to
9999).
The master key code is located in Appendix A.
Fill out and cut the part of the Appendix A reserved to
the security codes if it is desired to keep them secrets.

C. End = End configuration
This parameter allows to come back to the run time mode.
NO =

the instrument remains in configuration mode and
comes back to the first display of the configura-
tion mode (dF.Cn).

YES =

This selection ends the configuration mode. the
instrument performs an automatic reset and
restart the run time mode.

P50 - Set point access
0

only SP is accessible.

1

only SP and SP2 are accessible.

2

all 4 set points are accessible.

P51 = "Loop break alarm" function.
dIS =

Alarm not used

Enb =

The alarm condition of the "Loop break alarm"
(LBA) will be shown by the OUT 4 LED only.

EnbO = The alarm condition of the "Loop break alarm"

(LBA) will be shown by the OUT 4 LED and by
the OUT 4 relay status.

NOTES:
1) When the loop break alarm is enabled, the alarm 3 will

be automatically disabled.

2) The alarm 2, the alarm 3 and the "Loop break alarm"

are in OR condition on the same output (OUT 4).

3) The OUT 4 action type is programmed by P28

parameter.

4) The loop break alarm reset type is programmed by

P12 parameter.

5) For more details see "Loop Break Alarm function" at

pag 19.

P52 = Loop break alarm deviation
This parameter is available only when P51 is different
from "diS".
Range: from 0 to 500 units.

P53 =

Loop break alarm time.

This parameter is available only when P51 is different
from "dIS".
Programmable from 00.01 to 40.00 mm.ss.

P54 = Loop break alarm hysteresis.
This parameter is available only when P51 is different
from "dIS".
Programmable from 1to 50% of the power output.